background image

Appendix A Sensor calibration 

Nominal Resistance at 25˚C

All temperature sensors used by Heatmaster are NTC temperature sensors (NTC resistors – 

N

egative 

T

emperature 

C

oefficient). The sensors are simply made of one resistor, which alters under 

the influence of measuring physical values (in this case the temperature). The value is given in Ohm 
and can be adapted to specific manufacturer’s instructions. Frequently the value is given by 25˚C or 
can be taken out from the tables of data specifications or the curve chart. 

Sensor calibration

The more accurate you want to measure, more operative points to be considered. In this case it is 
suggestive to calibrate sensors individually.
The calibration can be done by electrical Ohm-meters, by which the Rn is calculated at 25˚C itself. 
For that You need a calibrated reference thermometer and a medium like water in a container with 
25˚ C of temperature. If the reference thermometer shows the 25˚ C water temperature, dip  the 
sensor, which has to be calibrated, in the water and notice the indicated value (in Ohm) after 30 
seconds. Enter this value under the variable “Nominal Resistance at 25˚ C”. The input of the real 
Resistance in Ohm enables the accurate measuring relatively within the scope of possibilities of 
NTCs.  25˚ C is therefore a good average value, as this is close to the room temperature and 
general measuring range. Rather distant “Reference points” from that could mean higher deviations 
from the real temperature. 

Reference thermometer calibration

 

If you have an accurate digital thermometer (more accurate than the normal NTC thermo sensors), 
which allows calibration, you can follow these instructions: 
Fill a container with ice cubes. Fill cold water in and stir it for about 1 minute. The water temperature 
is now 0°C. Dip the digital thermometer, wait 30 seconds and setup 0°C in the digital thermometer.
Qualitative first-class sensors can be identified with the availability of respective information in data 
specification. Further important values are tolerance data for nominal resistance, which can have 
abso/- 1°C as well as tolerance of beta-value. Sensors with very good beta-tolerance-values 
and tolerances provide more often higher accuracy and reliability in the whole working temperature-
scope. 
Using a calibrated thermometer (e.g. bulb thermometer from laboratory) is more precise but also 
more expensive.

Self calculating of the Beta-value 

   

Normal NTC-sensors (for measuring air- and water temperature) of the PC-field don’t posses data 
for beta-value. To intercept this disadvantage, some standard sensors are adjusted with different 
measurements and formulas to counteract the nonlinearity of NTC-sensors and to enable accurate 
measuring from the beginning. This leads to the default value of 3435 in the property “

Constant b

”.

If component-specific Beta value should be calculated, the Resistance at two different temperatures 
should be measured and the beta-value can be calculated with the use of a formula. Three different 
temperatures are much better.

Example 2: Temperature points measuring. 
For the beta-value in the desired temperature range for e.g. from 20°C - 100°C, one reading should 
be done at 20°C and the other at 100°C. With that other ranges such as 0°C and 80°C or more 
precise closer ranges are viable.

NTC thermal resistors are nonlinear resistors, which change their resistance with the temperature. 
The resistance decrease with the heat. How exact this nonlinear gradient looks is described in a 
constant, which is popular as beta (b)-value in the thermal resistor industry. The value is calculated 
as follows based on the formula given below.

 
  

29

Summary of Contents for Heatmaster

Page 1: ...ALPHACOOL HEATMASTER Measure Control Monitor Alarm Protect PC independent User guide V 1 0...

Page 2: ...tware 8 Quick start up 11 Appendix 1 Application of control loops 17 Appendix 2 Alarm conditions 18 Appendix 3 Controlling pumps with Heatmaster 19 Part 2 Heatmaster software functions Basics and menu...

Page 3: ...ing tone system alarm on main board BIOS shut down PC Windows drag and drop user interface Graphic display of delta values from two temperature sensors Log function of temperatures and fan pump values...

Page 4: ...surface of the Heatmaster carrier plate 2 Stick the Velcro counterpart on the desired place This can be somewhere in the casing or in an external place external cooling system as the Heatmaster doesn...

Page 5: ...function thereby hasn t changed 2 Relays Connect here a device of your choice or a further relay The Heatmaster relay delivers max 24 Volt 30 Watt of switching voltage ATTENTION Don t connect 110 220...

Page 6: ...Heatmaster usage on your own risk 7 Power connector Connect here 4 pin socket cable of your PC power unit ATTENTION if you operate 4 consumers pumps or and fans you need 96 Watt already Consider the w...

Page 7: ...connect the USB cable now Starting software or integration in to the autostart windows file after setting up personal settings control loops are also not necessary The Heatmaster consumes no PC resour...

Page 8: ...d after the installation of the drivers so the port is accessible 2 Driver installation The Heatmaster hardware will be found and Windows will ask for a suitable driver Confirm or give manually the cu...

Page 9: ...ny way The driver installation takes place for USB and thereafter for the serial port If the driver does not show the indicated functions uninstall the driver and restart the PC Start the driver insta...

Page 10: ...l port selected by the driver Select the relevant port With that the general installation of the Heatmaster is completed If you don t have a port to select check the driver installation and the correc...

Page 11: ...rther background information of your cooling configuration and control loops With this quick introduction you learn only basic functions needed for this example You get the complete information in par...

Page 12: ...te different functions in the control loop panel Button 1 indicates the device icons components of this control loop This is the standard display at the program start The configuration will be showed...

Page 13: ...ected during the first run The internal temperature sensor is in the monitor content by default and is displayed as a graph on the monitor The fan and one connected pump run with the full operating vo...

Page 14: ...lick button 3 you can see the properties of each components which are selected actually with miniature symbols in the configuration In the picture left the loop itself the frame around the miniature s...

Page 15: ...cs of controlling fans pumps Example the currently measured temperature could be the temperature of your CPU air cooler if the CPU is in idle running e g 50 C The sensor is also located on the heat si...

Page 16: ...are highlighted with star require hardware restart of microcontrollers from the file menu VIII Customization of speed pulses The number of the Pulse per rotation of pumps with Tachosignal and of some...

Page 17: ...nd instance is local control loops e g a fan and the relative thermo sensor direct on the graphic card CPU RAM Voltage transformer or on the hard disc Generally it is to consider that more local contr...

Page 18: ...perature or rather turned out Also an absence of the signal from a flow sensor could trigger the alarm The fans pumps are switched to 100 PWM and default values e g maximum PWM 80 are ignored Stage 2...

Page 19: ...pumps an optionally obtainable adapter cable is necessary of which the big 4 pin mole plug and 3 pin fan plug with the Tachosignal are adapted and consolidated on a 3 pin fan plug The pump reacts the...

Page 20: ...HEATMASTER INSTRUCTION MANUAL PART 2 EXTENDED SETUP...

Page 21: ...10 11 12 DRAG DROP Basically select all basic functions and devices from the library 5 through drag and drop with the mouse over 4 and 12 one of the five possible control loops 13 and deposit back the...

Page 22: ...are sent from Heatmaster to software All device icons dropped by mouse in Monitor content 4 are displayed also in the Monitor 2 as graphs The shortest interval is 2 seconds and the longest is 60 secon...

Page 23: ...the temperature can be seen S End End and S Delete and End S Actualize auto fit the graphs in monitor End Same function like S but with another zoom factor End and S Valid only for the last graph Del...

Page 24: ...of five loops The flow meter is used to calculate and control the liquid transportation in liquid cooling systems in liters or gallons Device Properties Rounds Actual RPM value is displayed Achieved...

Page 25: ...rt to work if the graphic card is in load modus full efficiency through a game or video encoding The temperature behavior of the PC should be observed here after 1 hour of minimum during the PC is in...

Page 26: ...red RPM Rounds Per Minute value Peak value Serves as reference and can be used for scaling Actual PWM Shows the actual value in a percentage This value can be changed manually if the control loop is d...

Page 27: ...can determine the time in which the results of fans should be evaluated You can determine the time individually Tacho signal available This property shows whether the connected fan posses a Tacho sig...

Page 28: ...ill not be triggered no data is evaluated such as RPM temperature etc and the fans are not controlled but will run in a manual modus over the property actual PWM Activate Alarm buzzer Shows the tone s...

Page 29: ...tir it for about 1 minute The water temperature is now 0 C Dip the digital thermometer wait 30 seconds and setup 0 C in the digital thermometer Qualitative first class sensors can be identified with t...

Page 30: ...described range This is not the most accurate way to calculate R for the temperature curve Another more accurate method is the Steinhart Hart equation in which three temperatures are used in one given...

Page 31: ...of 1 C above the nominal value At 1 C below the nominal value the fan will be switched off at latest after 10 minutes dT Temperature deviation from nominal value in C without prefix t Time to run thr...

Page 32: ...factor The amplification factor multiplies the temperature deviation from the nominal value An amplification factor below 1 cause attenuation of control loop a value of 1 deactivates the use of ampli...

Page 33: ...ts which occur from a possible refitting of products will not be overtaken by Alphacool 7 The warranty does not include following 7 1 Regular controlling maintenance and repair of the spare and wear p...

Page 34: ...o a well installed and secured push socket or to other power resource which is allowed by Alphacool Do not change the original parts or follow the instruction of this manual RoHS All parts of the Heat...

Reviews: