15
C048-781-30 R01, Rev. B (01/2020)
5.2.3
5.2.3 Alarm Indication
Alarm Indication
If an alarm occurs, press the alarm icon at the top left of the
screen to access the System Alarms screen.
Table 12. Alarm Indication
ALARM
ICON
COLOR
STATUS
Red
At least 1 major alarm has been
detected
Orange
At least 1 minor alarm and no major
alarms
5.2.3.1
5.2.3.1 System Alarms
System Alarms
This screen displays the bus/module/breaker location of the
alarm(s) and alarm type(s) as well as the total number of
alarms detected. Press the alarm silencer icon at the top left of
the screen to temporarily disable the audible alarm.
Table 13. Alarm Status
BACKGROUND COLOR STATUS
Red/White Gradient
At least one major alarm has
been detected
Orange/White Gradient
At least one minor alarm has
been detected, and no major
alarm
5.3
5.3 Module Detail
Module Detail
To access this screen, press any breaker status icon.
5.3.1
5.3.1 Individual Breaker Load and Ampacity
Individual Breaker Load and Ampacity
Table 14. Breaker Status
BREAKER
COLOR
STATUS
Gray
Breaker not installed and if installed,
breaker is OFF and not inventoried
Green
Normal operation and breaker is in
inventory
Light Orange
Breaker not inventoried but turned ON
(no alarms monitored)
Orange
Breaker in minor alarm and only
monitored for inventoried breakers
(breaker overload warning)
Red
Breaker in major alarm and only
monitored for inventoried breakers
(breaker overload or breaker trip)
Alarm
silencer
Module
Breaker
Bus
Total # of
alarms
present
Figure 15. System Alarms
Breaker status
Breaker ampacity
Breaker load
Figure 16. Module Detail