Table G — Specifications for 120 V models
Model number
AILI 750 VA
AILI 1000 VA
AILI 1500 VA
AILI 2200 VA*
AILI 3000 VA
Power rating, VA/W
750 VA
750 W
1000 VA
900 W
1500 VA
1350 W
1920 VA*
1920 W*
3000 VA
2700 W
Dimensions, W x D x H (mm)
Unit
440 x 405 x 88
440 x 650 x 88
Shipping
560 x 526 x 228
560 x 833 x 228
Weight (kg)
Unit
28
28
29
45
48
Shipping
31
31
31
47
50
Input AC Parameters
Surge protection
570 J
Voltage range without
battery operation
83 to 159, configurable
Frequency range
45 ~ 65 Hz, (±0.5 Hz)
Input power cord
10 ft (3 m) attached
w/ NEMA 5-15P
10 ft (3 m) attached
w/ NEMA 5-20P
10 ft (3 m) attached
w/ NEMA L5-30P
Output receptacles
(8) NEMA 5-15R
(6) NEMA 5-15R
(2) NEMA 5-20R
(6) NEMA 5-15R
(2) NEMA 5-20R
(1) NEMA L5-30R
Voltage (normal mode)
110 / 120 / 127 VAC (configurable) ±10%
Voltage (battery mode)
110 / 120 / 127 VAC (configurable)
Transfer time
4 to 6 ms typical
Waveform
Sine wave
Frequency (normal
mode)
45 to 65 Hz, (±0.5 Hz)
Frequency (battery
mode)
50 / 60 Hz, (±0.5 Hz), auto sensing
Overload Warning
Normal mode
> 100% to 109%
Continuous overload alarm and power to the load
> 110% to 120%
Shutdown after 10 minutes
>120%
Shutdown UPS immediately
Battery mode
> 100% to 119%
Continuous overload alarm until end of battery discharge
> 120% to 130%
Shutdown after 10 seconds
>130%
Shutdown UPS immediately
Battery Parameters
Model number
AILI 750 VA
AILI 1000 VA
AILI 1500 VA
AILI 2200 VA*
AILI 3000 VA
Quantity
3 pcs
3 pcs
3 pcs
6 pcs
6 pcs
Battery voltage
12 V
12 V
12 V
12 V
12 V