TROUBLE SHOOTING

 

 

Problem

 

LCD/LED/Buzzer

 

Explanation / Possible cause

 

What to do

 

Unit  shuts  down 
automatically 
during 

startup 

process. 

LCD/LEDs 

and 

buzzer  will  be  active 
for  3  seconds  and 
then complete off. 

 

The battery  voltage  is  too  low 
(<1.91V/Cell) 

 

1.  Re-charge battery. 
2.  Replace battery. 

 

No response after 
power on. 

 

No indication. 

1.  The  battery  voltage  is  far 

too low. (<1.4V/Cell) 

2.  Internal fuse tripped. 

1.  Contact repair center for 

replacing the fuse. 

2.  Re-charge battery. 
3.  Replace battery. 

 
 
 
 

Mains  exist  but 
the  unit  works  in 
battery mode. 

Input 

voltage 

is 

displayed as 0 on the 
LCD  and  green  LED 
is flashing. 

 

Input protector is tripped 

Check  if  AC  breaker  is 
tripped  and  AC  wiring  is 
connected well. 

 

 

Green LED is 
flashing. 

 

 

Insufficient 

quality 

of 

AC 

power. (Shore or Generator) 

1.  Check  if  AC  wires  are 

too thin and/or too long. 

2.  Check  if  generator  (if 

applied)  is  working  well 
or if input voltage range 
setting 

is 

correct. 

(UPS

Appliance) 

Green LED is 
flashing. 

Set 

“SUB”  (solar  first)  as  the 

priority of output source. 

Change 

output 

source 

priority to 

“USB” (utility first). 

When  the  unit  is 
turned on, internal 
relay  is  switched 
on 

and 

off 

repeatedly. 

 

LCD 

display 

and 

LEDs are flashing 

 

 

Battery is disconnected. 

 

Check  if  battery  wires  are 
connected well. 

 
 
 
 
 
 
 
 
 
 
 
 

 

Buzzer 

beeps 

continuously  and 
red LED is on. 

 
 
 

Fault code 07 

Overload error. The inverter is 
overload 110% and time is up. 

Reduce the connected load 
by 

switching 

off 

some 

equipment. 

If  PV  input  voltage  is  higher 
than  specification,  the  output 
power  will  be  derated.  At  this 
time,  if  connected  loads  is 
higher    than    derated    output 
power, it will cause overload. 

 

Reduce  the  number  of  PV 
modules  in  series  or  the 
connected load. 

 

 

Fault code 05 

 

Output short circuited. 

Check if wiring is connected 
well  and  remove  abnormal 
load. 

Temperature 

of 

internal 

converter  component  is  over 
120°C. 

Check  whether  the  air  flow 
of  the  unit  is  blocked  or 
whether 

the 

ambient 

temperature is too high. 

Fault code 02 

Internal temperature of inverter 
component is over 100°C. 

 

Fault code 03 

Battery is over-charged. 

Return to repair center. 

 

The battery voltage is too high. 

Check  if  spec  and  quantity 
of 

batteries 

are 

meet 

requirements. 

Fault code 01 

Fan fault 

Replace the fan. 

 

Fault code 06/58 

Output 

abnormal 

(Inverter 

voltage  below  than  190Vac  or 
is higher than 260Vac) 

1.  Reduce  the  connected 
load. 
2. Return to repair center 

Fault code 
08/09/53/57 

Internal components failed. 

Return to repair center. 

Fault code 51 

Over current or surge. 

Restart  the  unit,  if  the  error 
happens 

again, 

please 

return to repair center. 

Fault code 52 

Bus voltage is too low. 

Summary of Contents for SPCIII6000-48

Page 1: ...SPCIII6000 48 Solar inverter charger USER MANUAL...

Page 2: ...munication 13 Dry Contact Signal 13 OPERATION 14 Power ON OFF 14 Operation and Display Panel 14 LCD Display Icons 15 LCD Setting 17 Display Setting 28 Operating Mode Description 33 Battery Equalizatio...

Page 3: ...It s very important to correctly operate this inverter charger 8 Be very cautious when working with metal tools on or around batteries Dropping a tool could spark or short circuit batteries or other...

Page 4: ...generator power Auto restart while AC is recovering Overload Over temperature short circuit protection Smart battery charger design for optimized battery performance Cold start function Removable LCD...

Page 5: ...10 Battery input 11 Circuit breaker 12 Remote LCD panel communication port 13 Dry contact 14 USB communication port 15 BMS communication port CAN and RS232 or RS485 16 RS 232 communication port 17 Ou...

Page 6: ...ider the followings before selecting your placements Do not mount the inverter on flammable construction materials Mount on a solid surface Install the inverter at eye level in order to allow easy LCD...

Page 7: ...nection device in some applications however it s still recommended to have over current protection installed Please refer to typical amperage as required WARNING All wiring must be performed by a qual...

Page 8: ...ease choose a suitable battery cable with correct connector which can well fit into the battery terminals refer to recommended cable size table Apply ring terminals to your battery wires and secure it...

Page 9: ...reaker is 50A for SPCIII6000 48 CAUTION There are two power terminal blocks with IN Input and OUT Output markings DO NOT mistakenly connect to the wrong connectors WARNING All wiring must be performed...

Page 10: ...5 Make sure the wires are securely connected PV Connection CAUTION Before connecting to PV modules please install a separately DC circuit breaker between the inverter and PV modules WARNING It s very...

Page 11: ...tions are listed in the table below SOLAR INPUT Q ty of panels Total input Solar Panel min in series 6 pcs max in series 12 pcs power 6 pcs in series 6 pcs 1500W Spec reference 8 pcs in series 8 pcs 2...

Page 12: ...moved and installed in a remote location with an optional communication cable Please take the following steps to implement this remote panel installation Step 1 Remove the screw on the bottom of LCD p...

Page 13: ...holes in the marked locations as shown in the illustration below The LCD module then can be securely mounted to your desired location 5 9 Step 3 Connect LCD module to the inverter with an optional RJ4...

Page 14: ...please check Appendix C BMS Communication It is recommended to purchase a special communication cable if you are connecting to Lithium Ion battery banks Please refer to Appendix B BMS Communication I...

Page 15: ...output power information Setting LED 2 LCD display Setting LED 1 Function keys Setting LED 3 Status indicators Function keys On off switch Indicators LED Indicator Color Solid Flashing Messages Setti...

Page 16: ...Icons Icon Function description Input Source Information Indicates the AC input Indicates the PV input Indicate input voltage input frequency PV voltage charger current charger power battery voltage C...

Page 17: ...de it will present battery capacity Load Percentage Battery Voltage LCD Display Load 50 1 85V cell 1 85V cell 1 933V cell 1 933V cell 2 017V cell 2 017V cell Load 50 1 892V cell 1 892V cell 1 975V cel...

Page 18: ...Solar energy provides power to the loads as first priority If solar energy is not sufficient to power all connected loads Utility energy will supply power to the loads at the same time SBU priority S...

Page 19: ...29 Pylontech battery If selected programs of 02 26 27 and 29 will be automatically set up No need for further setting WECO battery only for 48V model If selected programs of 02 12 26 27 and 29 will b...

Page 20: ...d occurs Restart disable default Restart enable 07 Auto restart when over temperature occurs Restart disable default Restart enable 09 Output frequency 50Hz default 60Hz 10 Output voltage 220V 230V de...

Page 21: ...ram 01 Battery fully charged 54V default Setting range is from 48V to 58V Increment of each click is 1V 16 Charger source priority To configure charger source priority If this inverter charger is work...

Page 22: ...and sufficient 18 Alarm control Alarm on default Alarm off 19 Auto return to default display screen Return to default display screen default If selected no matter how users switch display screen it w...

Page 23: ...lk charging voltage C V voltage SPCIII6000 48 default setting 56 4V If self defined is selected in program 5 this program can be set up Setting range is from 48 0V to 61 0V for SPCIII6000 48 model Inc...

Page 24: ...0V for SPCIII6000 48 model Increment of each click is 0 1V Low DC cut off voltage will be fixed to setting value no matter what percentage of load is connected 30 Battery equalization Battery equaliza...

Page 25: ...battery equalization immediately and LCD main page will shows If Disable is selected it will cancel equalization function until next activated equalization time arrives based on program 35 setting At...

Page 26: ...31 98 Time setting Month For month setting the range is from 1 to 12 99 Time setting Year For year setting the range is from 17 to 99 Functional Setting There are three function keys on the display pa...

Page 27: ...e check with your dealer or installer for detail instructions By pressing button to export data log from the inverter to USB disk If Export data log the selected function is ready LCD will display Pre...

Page 28: ...ess button to set up Solar First Timer Press button to select staring time Press or button to adjust values and press to confirm Press button to select end time Press or button to adjust values press...

Page 29: ...to adjust values press button to confirm The setting values are from 00 to 23 with 1 hour increment Press button to set up Solar Only Timer Press button to select staring time Press or button to adjus...

Page 30: ...Page 29 to 62 Selectable information LCD display PV current PV current 2 5A PV power PV power 500W Charging current AC and PV charging current 50A PV charging current 50A AC charging current 50A...

Page 31: ...play Charging power AC and PV charging power 500W PV charging power 500W AC charging power 500W Battery voltage and output voltage Battery voltage 25 5V output voltage 230V Output frequency Output fre...

Page 32: ...ll present x xkVA like below chart Load in Watt When load is lower than 1kW load in W will present xxxW like below chart When load is larger than 1kW 1KW load in W will present x xkW like below chart...

Page 33: ...energy 988kWh PV energy generated this year and Load output energy this year This PV year energy 3 88MWh Load year energy 9 88MWh PV energy generated totally and Load output total energy PV Total ener...

Page 34: ...erating Mode Description Operation mode Description LCD display Charging by utility and PV energy Standby mode Charging by utility Note Standby mode The No output is supplied by inverter is not turned...

Page 35: ...ailable Grid and PV power are available Grid is available PV power is available No charging Line Mode The unit will provide output power from the mains It will also charge the battery at line mode Cha...

Page 36: ...elected as output source priority and battery is not connected solar energy and the utility will provide the loads Power from utility Battery Mode The unit will provide output power from battery and o...

Page 37: ...ttery equalization function in LCD setting Program 30 first You can then apply this function by either one of the following methods 1 Setting equalization interval in Program 35 2 Activate equalizatio...

Page 38: ...ion and return to the floating charging stage Fault Reference Code Fault Code Fault Event Icon on 01 Fan is locked when inverter is off 02 Over temperature 03 Battery voltage is too high 04 Battery vo...

Page 39: ...over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds 15 PV energy is low Beep twice eve...

Page 40: ...Voltage 270Vac 7V Max AC Input Voltage 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High Loss Return F...

Page 41: ...cy 93 Overload Protection 5s 110 load 10s 105 110 load Surge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 48Vdc Cold Start Voltage 46 0Vdc Low DC Warning Voltage 46 0Vdc 44 0Vdc load...

Page 42: ...nt Time Bulk Absorption Maintenance Constant Current Constant Voltage Floating MPPT Solar Charging Mode INVERTER MODEL SPCIII6000 48 Max PV Array Power 6000W 360Vdc Nominal PV Voltage Start up Voltage...

Page 43: ...Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is overload 110 and time is up Reduce the connec...

Page 44: ...ification Reduce the number of PV modules in series Appendix A Approximate Back up Time Table Model Load VA Backup Time 48Vdc 100Ah min Backup Time 48Vdc 200Ah min SPCIII6000 48 500 613 1288 1000 268...

Page 45: ...arging according to the status of lithium battery 2 Pin Assignment for BMS Communication Port 3 AOESS48 LFP4100 Lithium Battery Communication Configuration Dial switch address Used to set the address...

Page 46: ...the RS485 port Step 2 Switch on Lithium battery by pressing the reset button Step 3 Turn on the inverter Step 4 Be sure to select battery type as Lib in LCD program 5 If communication between the inv...

Page 47: ...ach battery module by rotating the PIN number on the ID switch From number 0 to 9 the number can be random no particular order Maximum 10 battery modules can be operated in parallel Installation and O...

Page 48: ...secs the battery module will start up If the manual button cannot be approached just simply turn on the inverter module The battery module will be automatically turned on Step 5 Turn on the inverter...

Page 49: ...quired to set up master battery with this setting and slave batteries are unrestricted 1 0 0 Multiple group condition It s required to set up master battery on the first group with this setting and sl...

Page 50: ...is ready Step 4 Turn on the inverter Step 5 Be sure to select battery type as PYL in LCD program 5 If communication between the inverter and battery is successful the battery icon on LCD display will...

Page 51: ...tep 2 Switch on Lithium battery Step 3 Turn on the inverter Step 4 Be sure to select battery type as WEC in LCD program 5 If communication between the inverter and battery is successful the battery ic...

Page 52: ...n DC isolator and switch on Lithium battery Step 3 Turn on the inverter Step 4 Be sure to select battery type as SOL in LCD program 5 If communication between the inverter and battery is successful th...

Page 53: ...tery Communication lost only available when the battery type is setting as Pylontech Battery After battery is connected communication signal is not detected for 3 minutes buzzer will beep After 10 min...

Page 54: ...ing Wi Fi module with WatchPower APP available for both iOS and Android based device All data loggers and parameters are saved in iCloud The major functions of this APP Delivers device status during n...

Page 55: ...l in all required information and scan the remote box PN by tapping icon Or you can simply enter PN directly Then tap Register button Then a Registration success window will pop up Tap Go now to conti...

Page 56: ...nter default password 12345678 Then return to WatchPower APP and tap button when Wi Fi module is connected successfully Step 3 Wi Fi Network settings Tap icon to select your local Wi Fi router name to...

Page 57: ...module is not monitoring properly please tap on the top right corner of the screen for further details It will show repair suggestion Please follow it to fix the problem Then repeat the steps in the c...

Page 58: ...gistered name and password to login Note Tick Remember Me for your login convenience afterwards Overview After login is successfully you can access Overview page to have overview of your monitoring de...

Page 59: ...ce Delete device Tap icon on the top right corner and manually enter part number to add device This part number label is pasted on the bottom of remote LCD panel After entering part number tap Confirm...

Page 60: ...d Clear cache and Log out shown as below diagrams 2 4 Device List In Device List page you can pull down to refresh the device information and then tap any device you want to check up for its real time...

Page 61: ...andby mode Line Mode Inverter will power the load from the utility with or without PV charging Qualified utility or PV source can charge battery Battery Mode Inverter will power the load from the batt...

Page 62: ...and Load percent Please slide up to see more basic information Production Information displays Model type Inverter type Main CPU version Bluetooth CPU version and secondary CPU version Rated Informati...

Page 63: ...models Please always see the original product manual for detailed setting instructions Parameter setting list Item Description Output setting Output source priority To configure load power source prio...

Page 64: ...1 minute Bypass Function If enabled unit will transfer to line mode when overload happened in battery mode Beeps while primary source interrupt If enabled buzzer will alarm when primary source is abno...

Reviews: