3.
UPS Functional Descriptions
3.1.
Front Panel Display
3.1.1. CONTINUITY PLUS < Convertible Type (Rack / Tower) < LED Panel
(Standard)
Control Key
Symbol
Description
ON(Alarm Silence)
a. UPS Power-On Switch
(Press and hold until the buzzer beeps.)
b. Alarm silence
c. Error Code Display Function Mode
After an alarm, press to mute the alarm buzzer and
show an Error Code. (Do not hold for > 1 second.)
OFF
UPS Power-Off Switch
(Press and hold until the buzzer beeps.)
Self-Test
a. Commands the UPS to perform self-testing
(Press and hold until the buzzer beeps.)
b. Battery and Load Display Function Mode (Do
not hold for > 1 second.)
◎
Manual Bypass
+
Press the "ON" key and "Self-Test" key simultaneously
for three seconds to transfer from "Inverter to Bypass"
(The bypass LED will continuously blink and the buzzer
will beep intermittently.) or "Bypass to Inverter" when
the UPS is in on-line mode and the Bypass Voltage
Window is Normal.
LED Indicator
Symbol
Description
Normal Mode LED
1. Solid indicates normal utility voltage.
Blinking indicates insufficient utility voltage
for the full load. Off indicates abnormal utility
voltage.
2. In Battery and Load Function Mode
indicates battery capacity is 50%.
Battery Mode LED
1. Indicates load supplied by battery power.
2. In Battery and Load Function Mode
indicates battery capacity is 25%.
Bypass Mode LED
1. Indicates load supplied by bypass.
2. In Battery and Load Function Mode
indicates battery capacity is 75%.
Battery
Bad/Weak LED
1. Indicates low battery power or faulty
battery bank.
2. In Battery and Load Function Mode
indicates battery capacity is 100%.
Fault LED
1. Solid indicates fault or abnormal condition.
2. Blinking indicates LED Panel in Error
Code Function Mode.
Overload LED
1. Indicates UPS is overloaded.
2. In Error Code Function Mode indicates
Error Code 16.
Site wiring fault LED
1. Indicates live and neutral lines are
connected wrongly or high neutral-ground
voltage.
2. In Battery and Load Function Mode
indicates load capacity is 100%.
3. In Error Code Function Mode indicates
Error Code 8.
Outlet1 LED
1. Indicates UPS Outlets 1 are enabled and
ready to supply loads. (This function is
optional.)
2. In Battery and Load Function Mode
indicates load capacity is 75%.
3. In Error Code Function Mode indicates
Error Code 4.
Page
8
to
47
Page
9
to