Check evaporator and condensate pan
and clean if required
1. Remove the front panel and the cover, thus gain-
ing access to the cleaning opening (1).
2. After the cover is removed (1), the entire conden-
sate pan area before (2) and after (3) the evapora-
tor is visible and can be cleaned if necessary.
Heat source
inlet sensor
As an alternative, the lateral air ducts, the side walls,
the louvre grilles and blind covers can be removed (if
necessery also the fan module) , to obtain better ac-
cess.
“Optional disconnection of the fan module“,
page 9
12.3
Clean and flush condenser
► Clean and flush the condenser in accordance with
the manufacturer's instructions.
► After flushing the condenser with chemical
cleaning product: neutralise any residues and
flush the condenser thoroughly with water.
12.4 Yearly maintenance
►
Record the quality of the heating water analytically.
In case of deviations from the specifications, take
suitable measures without delay.
13 Faults
►
Read out the cause of the fault via the diagnostics
program of the heating and heat pump controller.
►
Contact the local partner of the manufacturer or
the factory's customer service. Have the fault
message and unit number to hand.
“Nameplate“, page 7
14 Dismantling and disposal
14.1 Dismantling
Unit is safely disconnected from the power supply
and secured against being switched back on
again.
►
Collect all media safely.
►
Separate components by their materials.
14.2 Disposal and recycling
►
Dispose of environmentally hazardous media in
accordance with local regulations (e.g. refrigerant,
compressor oil).
►
Recycle or ensure proper disposal of unit
components and packaging materials in
accordance with local regulations.