Subject to technical amendments without prior notice  |  83055800cUK – Translation of the operating manual |  ait-deutschland GmbH

5.4  Installation

Preparation for installation, together with 

the wall duct

To connect the outdoor unit to the indoor part (hydraulic 

unit), there must be a suitable opening for the wall duct 

(accessory) or an opening has to be cut out in order to 

insert the Ø125 mm waste water pipe (= wall duct ac

-

cessory).

If the wall duct is not yet present, you can also use a 

commercially available waste water pipe, length 1 m, 

DN 125 in advance.

 NOTE

Always comply with the installation plan for 

the respective device type. Observe the mini-

mum clearances and protected zones.

 

Installation plan, dimension drawings and scopes 

of protection for the respective device type.

 CAUTION

In the air outlet area the air temperature is 
approx. 5 K below the ambient temperature. 
Under certain climatic conditions, an ice layer 
can therefore develop in the air outlet area.
Install the heat pump so that the air coming 
from the air outlet opening is not discharged 
into footpath areas.

 NOTE

The surface in the air outlet area of the heat 

pump must be permeable to water.

If the wall duct is not used, the bus cable 

must be routed through a separate cable con-

duit, separated from the other cables.

The other two cables also have to be routed 

using empty conduits on site.

 NOTE

The noise immissions of the heat pumps must 

be taken into account in the respective instal-

lation plans for air/water heat pumps. The re-

spective regional regulations must be complied 

with.

5.3  Unpacking and transport

Notes on safe transport

The device is heavy (

 

“Technical data/scope of de-

livery” on page 15). There is a risk of injuries or ma-

terial damage if the device falls down or overturns.
There is a risk of cutting your hands on sharp edges of 

the device.

 

Wear cut resistant protective gloves.

The hydraulic connections are not designed for mechan-

ical loads.

 

Do not lift or transport the device by the hydraulic 

connections. 

Transport the device with a pallet truck if possible, or 

alternatively carry it

 

Do not tilt the heat pump by more than 45°.

Transport with a pallet truck

 

Transport the device to the installation site in 

packaged form, and secured on a wooden pallet.

Unpacking:

1. 

Remove plastic films. Make sure that you do not 

damage the device when doing this.

2.  Dispose of the transport and packaging material in 

an environmentally sound manner and in accord-

ance with local regulations.

Carrying the device

 NOTE

The device is delivered on a pallet with mount-

ing rails. The mounting rails can be used for 

transport.

Mounting rail

Summary of Contents for LWDV

Page 1: ...UK Operation manual LWDV Air water heat pumps Dual outdoor installation 83055800cUK Translation of the operating manual...

Page 2: ...11 8 Flushing filling and venting 12 8 1 Heating water quality 12 8 2 Flushing filling and venting the heating circuit 12 9 Insulation of hydraulic connections 12 10 Setting the overflow valve 12 11...

Page 3: ...Operation manual for the heating and heat pump controller Short description of the heat pump controller Operation manual for the extension board acces sory Operation manual for the hydraulic unit 1 3...

Page 4: ...juries and material damage Ensure that personnel are familiar with local regu lations especially those relating to working safely and in awareness of the hazard risks Have work on the electrical and e...

Page 5: ...ater heating systems Professional planning and commissioning Closed system with regard to corrosion Integration of an adequately dimensioned pres sure maintenance Use of demineralized water heat ing w...

Page 6: ...field installation an extension set can be ordered 3 3 Function Liquid refrigerant is evaporated evaporator The en ergy for this process is ambient heat coming from the outside air The gaseous refrig...

Page 7: ...ent washing up liquid neutral cleaning agent Do not use any aggressive abrasive acid or chlorine based cleaning agents 5 Delivery storage transport and installation ATTENTION Damage to the housing and...

Page 8: ...must be routed through a separate cable con duit separated from the other cables The other two cables also have to be routed using empty conduits on site NOTE The noise immissions of the heat pumps m...

Page 9: ...oad bearing walls In a timber frame construction with facing the floor bracket should be used due to the possible trans fer of structurally borne sound to the interior 5 6 Installation on a floor brac...

Page 10: ...must be ensured 2 Towards the inside Insert the condensate pipe wall duct accessory through the wall duct accessory using lubricant and connect it to the condensate nozzle using the enclosed plastic...

Page 11: ...c information relating to the electrical connection Any specifications by the local energy supply com pany apply to electrical connections Equip the power supply for the heat pump with an all pole min...

Page 12: ...ble to control individual circulation pumps and even the changeover valve via the venting programme As a result it is not necessary to remove the valve motor 1 Vent the system at the highest point 2 V...

Page 13: ...ergy supply company has been notified of the operation of the heat pump system 9 9 The system is air free 9 9 Installation check using the rough checklist has been completed successfully 1 Ensure that...

Page 14: ...fter flushing the condenser with chemical clean ing agent neutralise any residues and flush the condenser thoroughly with water 13 Malfunctions Read out the cause of the malfunction via the di agnosti...

Page 15: ...e min I max l h General unit data Total weight kg Weight of heat pump module I Compact module I Fan module kg I kg I kg Refrigerant type Refrigerant capacity kg Electrics Voltage code all pole fuse pr...

Page 16: ...maler Druckverlust Qh min max minimale maximale Heizleistung Pe min max Leistungsaufnahme bei minimaler maximaler Heizleistung Bezeichnung Seite 1 Zeichnungsnummer 823296 Datei 823296 Leistungs Druckv...

Page 17: ...0 C C 4x M8 IG 6 Legende D819504 Alle Ma e in mm A Vorderansicht B Seitenansicht von links C C Schnitt Grundplatte Technische nderungen vorbehalten A B 5 4 3 2 1 A B C D E F Schutzvermerk ISO 16016 be...

Page 18: ...befinden Der Schutzbereich darf sich nicht auf Nachbargrundst cke oder ffentliche Verkehrsfl chen erstrecken Die Wanddurchf hrung durch die Geb udeh lle ist gasdicht auszuf hren Abbildung Sicherheits...

Page 19: ...ry 8 Cladding of wall duct accessory 1320 930 300 93 FS 1800 A 1 2 X C W Y V UKG OKB 4 5 3 510 445 200 430 400 FS 800 FS 800 FS 1650 282 LR LRO FA 6 4 5 3 8 Legende 819393 1c Technische nderungen vorb...

Page 20: ...r 8 Verkleidung Wandkonsole Zubeh r 12 Hydraulische Verbindungsleitung V2 5 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F 4 3 2 1 c b a Zust nderungstext PEP 006 2011 PEP 003 2012 M 063 2...

Page 21: ...lauf siehe Bedienungsanleitung 7 Konsole f r Bodenbefestigung Zubeh r 8 Verkleidung Wanddurchf hrung Zubeh r Y X V 5 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F 4 3 2 1 c b a Zust nderun...

Page 22: ...eidung Bodenkonsole Zubeh r 12 Hydraulische Verbindungsleitung V4 Y Z A C V 5 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F 4 3 2 1 c b a Zust nderungstext PEP 006 2011 PEP 003 2012 M 063...

Page 23: ...icht W Detailansicht Wandbefestigung GK Ger tekontur 9 Bohrung f r Leerrohr KG DN125 a 125 10 Befestigungsbohrungen f r Wandkonsolen A 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F Key 819...

Page 24: ...gswand zu V2 A Vorderansicht W Detailansicht Wandbefestigung GK Ger tekontur 10 Befestigungsbohrungen f r Wandkonsolen A BB2 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F Drill template fo...

Page 25: ...t 14 Kondensatablaufrohr min 50 15 Befestigungsbohrungen f r Bodenkonsole Das Fundament darf keinen K rperschallkontakt zum Geb ude haben A C 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F...

Page 26: ...wasser Vor und R cklaufleitung A Z Das Fundament darf keinen K rperschallkontakt zum Geb ude haben 18 5 4 3 2 1 Schutzvermerk nach ISO 16016 beachten A B C D E F 4 3 2 1 c b a Zust nderungstext PEP 00...

Page 27: ...in mm FW2Functionally necessary minimum clearances C Top view FA Complete external facade LR Direction of air Minimum clearances 3000 3000 C LR FA FW2 Legende 819393 10c Technische nderungen vorbehal...

Page 28: ...ged frost free in all cases figure 1a and figure 1b 0 9m KS 3 0 9m 1b 3 1c 3 1a Legende 819400 1 Technische nderungen vorbehalten Aufstellungshinweise f r Anschlu der Kondensatleitung au erhalb des Ge...

Page 29: ...ured that the condensate is discharged frost free in all cases figure 2a 2a 2b Legende 819400 2 Technische nerungen vorbehalten Aufstellungshinweise f r Anschlu der Kondensatleitung innerhalb des Geb...

Page 30: ...30 Subject to technical amendments without prior notice 83055800cUK Translation of the operating manual ait deutschland GmbH Hydraulic integration with hydraulic station...

Page 31: ...31 Subject to technical amendments without prior notice 83055800cUK Translation of the operating manual ait deutschland GmbH Hydraulic integration with buffer tank in series and hydraulic module...

Page 32: ...32 Subject to technical amendments without prior notice 83055800cUK Translation of the operating manual ait deutschland GmbH Hydraulic integration of separation buffer tank...

Page 33: ...c hot water ZWE 28 Brine circulation pump VBO Additional circuit board 29 Dirt trap max 0 6 mm screen size 15 Mixing circuit three way mixer MK2 3 discharging 30 Collection container for brine mixture...

Page 34: ...ution box power supply 817449a BP1 F2 BP1 BP2 F1 BP2 BP T10 F3 RF1 R20 C1 X8 F6 1 G1 1 2 3 4 5 6 7 8 1 2 8 A B C D E F A B C D E F Blatt Bl 1 3 3 4 5 6 7 AIT 817449 Stromlaufplan ait deutschland GmbH...

Page 35: ...board Attention I max 6 3A 230VAC Defrosting valve Control voltage From hydraulic module 817449a K40 X1 X2 K21 1 2 3 4 5 6 7 8 1 2 8 A B C D E F Bl 3 4 5 6 7 AIT 817449 Stromlaufplan ait deutschland G...

Page 36: ...denser Sump heating sensor Heat source input sensor Hot gas sensor Suction sensor evaporator Encoding resistor R4 817449a R5 R9 21 5kOhm K22 X6 B10 X8 B11 X10 X11 1 2 3 4 5 6 7 8 A B C D E F A B C D E...

Page 37: ...37 Subject to technical amendments without prior notice 83055800cUK Translation of the operating manual ait deutschland GmbH...

Page 38: ...38 Subject to technical amendments without prior notice 83055800cUK Translation of the operating manual ait deutschland GmbH...

Page 39: ...3 2014 35 EU 814 2013 2014 30 EU 2014 68 EU EN 378 Designation of the device s 100699HDV901 100699HSDV901 100699HSDV1201 100699HDV1201 100 699 01 100 699 01 100 699 01 100 699 01 Unit model Item numbe...

Page 40: ...ait deutschland GmbH Industriestrasse 3 95359 Kasendorf Germany E info alpha innotec de W www alpha innotec de alpha innotec an ait deutschland GmbH brand UK...

Reviews: