12
Subject to change without notice | 83059000gUK – Translation of the original operating manual | ait-deutschland GmbH
Transporting the heat pump module with a
handcart
1. Load the heat pump module only with the narrow
side, left or right, on the handcart.
2. Secure the heat pump module to the handcart
with lashing straps.
3. Transport the heat pump module to the installation
site.
5.4 Installation
CAUTION
In the air outlet area the air temperature is
approx. 5° K below the ambient temperature.
Under certain climatic conditions an ice
layer can therefore form in the air outlet
area. Install the heat pump such that the
air blower does not discharge into footpath
areas.
Installation area and space requirements
NOTE
Note and follow the local regulations and
standards regarding the installation area and
space requirements. The table shows the
regulations to EN 378-1 relevant in Germany.
Refrigerant
Limit value [kg/m³]
R 134a
0.25
R 404A
0.52
R 407C
0.31
R 410A
0.44
R 448A
0.39
“Technical data / Scope of supply”, page 23
Minimum room volume =
Refrigerant capacity [kg]
Limit value [kg/m3]
NOTE
If several heat pumps of the same type are
installed only one heat pump need to be
taken into account. If several heat pumps of
different types are installed, only the heat
pump with the largest refrigerant volume
needs to be taken into account.
Minimum volume corresponds to the requirements
for the refrigerant used.
Installation inside the building only.
Installation area is dry and frost-free.
Clearance dimensions are met
(
“Installation plans”, page 31
The surface/floor is suitable for installation of the
unit:
●
Level and horizontal
●
Load-bearing capacity for the unit's weight