11
Subject to change without notice | 83061500bUK | ait-deutschland GmbH
16.3 Installation
“Dimensioned drawings”, page 28, and “Instal-
lation plan”, page 29
CAUTION
In the air outlet area the air temperature is
approx. 5 K below the ambient temperature.
Under certain climatic conditions, an ice la-
yer can therefore form in the air outlet area.
Install the heat pump such that the air blo-
wer does not discharge into footpath areas.
NOTE
Set up the unit so that the switch box side is
accessible at all times.
16.4 Attaching the air deflector hoods
WARNING
Rotating parts on the unit.
For safety reasons, mount the two air
deflector hoods on the unit before carrying
out any other work.
1. If you haven't done so already, remove the lower
facing panels from the switch box and water con-
nection side of the unit.
1.1. To do this, undo the two quick-release screws in
the lower facing panels.
1.2. Pull each of the facing panels upwards and out-
wards, lift them out of the unit frame and put in a
safe place.
1 Lower facing panels
Lifting the unit with a crane
1. Remove the strips on the sides of the wooden pal-
let.
2. Pass the roundslings under the unit. Place lengths
of timber between the roundslings and the unit to
prevent pressure damage to the housing, or dis-
mantle the facing panels (for dismantling instruc-
tions, see “Attaching the air deflector hoods”).
A Front view (operating side)
B Side view 1
WARNING
Roundslings should not be too close
together or too near the middle; otherwise
the unit may tilt or overturn!
IMPORTANT
Pass roundslings past the fan on the side.
Make sure that the loaded roundslings do not
press against the fan.
3. Lift the unit with the crane and place it on the
base. Make sure that the unit's baseframe is in full
contact with the base.
Summary of Contents for LW 161H-A
Page 1: ...UK 83061500bUK Air Water Heat Pumps Outdoor installation Operating Manual LW 161H A V...
Page 31: ...31 Subject to change without notice 83061500bUK ait deutschland GmbH Row tank LW 161H A V...
Page 38: ...38 Subject to change without notice 83061500bUK ait deutschland GmbH...
Page 39: ...39 Subject to change without notice 83061500bUK ait deutschland GmbH...