Specifications
66
900-0150-01-00 Rev A
Default Settings and Ranges
The settings in this table are as displayed in the MATE3 system display for a 12-volt system.
Table 10 FLEXmax Settings (MATE3)
Mode
Menu Item
Setting
Charger
Absorb Voltage
Default 14.4 Vdc
Range:
Float
setting to 80 Vdc
(Absorb) Time
Default 01.0 hours Range: 00.0 to 24 hours
Float
Default 13.8 Vdc
Range: 12.0 Vdc to
Absorbing
setting
Rebulk Voltage
Default 12.0 Vdc
Range: 12.0 Vdc to
Float
setting
Current Limit
Default 80 Adc
Range: 5 to 80 Adc
Absorb End Amps
Default 00 Adc
Range: 00 to 55 Adc
MPPT
MPPT Mode
Default
<Auto >
<Auto>
or
U-Pick>
U-Pick VOC
Default 77% Voc
Range: 40 to 90% Voc
Wakeup VOC Change
Default 1.5 Vdc
Range: 1.5 to 9.5 Vdc
(Wakeup VOC) Time
Default 05 minutes
Range: 05 to 15 minutes
Snooze Mode Amps
Default 0.6 Adc
Range: 0.2 to 1.0 Adc
MPP Range Minimum
Default <
Half>
<Half or Full>
(MPP Range) Maximum
Default
<90%>
<80, 85, 90, 99%>
Temperature
Compensation
Mode
Default
<Wide >
<Wide>
or
<Limited>
Slope
Default 5 mV
Range: 2 to 6 mV
Lower Battery Voltage
Default 14.1 Vdc
Range: 10 Vdc to
Upper Battery Voltage
setting
Upper Battery Voltage
Default 14.1 Vdc
Range:
Lower Voltage
setting to 80 Vdc
Battery Equalize
Equalization Voltage
Default 14.4 Vdc
Range:
Absorb Voltage
setting to 80 Vdc
(Equalization) Hours
Default 01 hours
Range: 1 to 7 hours
Automatic Battery Equalization
Default 0 days
Range: 0 to 250 days
Grid-Tie Mode
Enable Grid-Tie Mode
Default
N
Range:
Y
or
N
Auxiliary Output
Diversion:Relay
Default
<Off>
<On, Auto, Off>
Active
Default
Active High
Range:
Active High
or
Active Low
Relative
Voltage
Default 0.0 Vdc
Range: 0.0 to 5.0 Vdc
Hysteresis
Default 00.2 Vdc
Range: 0.0 to12.0 Vdc
Hold
Default 0.1 second
Range: 0.0 to 25 seconds
Delay
Default 0.0 seconds
Range: 0.0 to 24 seconds
Summary of Contents for OutBack Power FLEXmax Extreme Series
Page 1: ...FLEXmax Extreme Charge Controller Owner s Manual ...
Page 6: ...Table of Contents 4 900 0150 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...MATE MATE2 Screens 60 900 0150 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 70: ...Specifications 68 900 0150 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...