Installation and Operation
6
900-0227-01-00 Rev A
Materials Required
Tools (use insulated tools only)
o Digital
voltmeter
o
Socket wrench
o
Torque wrench calibrated in inch-pounds
o
Box end wrench
o
Battery lifting equipment (handles) and fork lift to lift pallets of batteries
o Rubber
gloves
o Full
face
shield
o Plastic
apron
o Portable
eyewash
o Spill
kit
o
Fire extinguisher (class C)
Accessories
o
Interconnect bar (included)
o
Terminal cover (included)
o Hardware
(included)
o
Interconnect cables as needed
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable ampacity
must meet the needs of the system, including temperature, deratings, and any other
code concerns.
Storage and Environment Requirements
Temperatures
o
To achieve maximum life of EnergyCell batteries, it is recommended not to operate them in
average ambient temperatures outside the range of 68°F to 86°F (20°C to 30°C). High operating
temperatures will shorten a battery’s life (see page 7).
o
Do not allow batteries to freeze, as this will damage them and could result in leakage.
o
Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
o
Batteries should be stored in a cool, dry location. The best storage temperature is 77°F (25°C), but
a range of –4°F to 104°F (–20°C to 40°C) is acceptable.