10

P.33

- Threshold beyond which the integral delay for tripping of the overload alarm is zeroed, causing the immediate intervention of the A08 alarm.

P.34 – P.35

– Data of VTs eventually used in the wiring diagrams.

Parameter table (continued)
P.37 – P.38

- Start and stop temperature for the cooling fan of the panel, expressed in the unit set by P.36.

P.39

- Threshold for generation of alarm A07 Panel temperature too high .

P.40

- Percentage threshold of the residual power of the steps, compared with the original power programmed in general menu. Below this threshold the

alarm A10 step failure is generated.

P.41

- Maximum voltage alarm threshold, referred to the rated voltage set with P.07, beyond which the alarm A06 Voltage too high is generated.

P.42

- Undervoltage alarm threshold, referred to the rated voltage set with P.07, below which the alarm A05 voltage too low is generated.

P.43

- Maximum plant voltage THD alarm threshold, beyond which the alarm A10 THDV too high is generated.

P.44

– Maximum plant current THD alarm threshold beyond which the alarm A05 voltage too low is generated.

P.45

– Maintenace interval in hours. When it is elapsed, the alarm A12 maintenance interval will be generated. The hours count increments as long as the

device is powered.

P.46

– Function of the semi-circular bar-graph.

Kvar ins/tot:

The bar graph represents the amount of kvar actually inserted, with reference to the total reactive power installed in the panel.

Curr act/nom:

Percentage of actual plant current with reference to the maximum current of the CT.

Delta kvar:

bar graph with central zero. It represents the positive/negative delta-kvar needed to reach the setpoint, compared to the total kvar installed.

P.47

– Default measure shown on the secondary display. Setting the parameter to ROT, the different measures will be shown with a sequential rotation.

P.48

– If set to ON, the display backlight flashes in presence of one or more active alarms.

P.49

– Serial (node) address of the communication protocol.

P.50

– Communication port transmission speed.

P.51

– Data format. 7 bit settings can only be used for ASCII protocol.

P.52

– Stop bit number.

P.53

– Select communication protocol.

ALARM MENU

Cod

Description

ACC

UoM

DEF

RANGE

P.61

Alarm activation A01

Adv

ALA

OFF

ON

ALA

DISC

A+D

P.62

Alarm delay A01

Adv

15

0-240

P.63

Delay UoM A01

Adv

min

Min

Sec

P.64

Alarm activation A02

Adv

ALA

OFF

ON

ALA

DISC

A+D

P.65

Alarm delay A02

Adv

120

0-240

P.66

Delay UoM A02

Adv

Sec

Min

Sec

P.67

Alarm activation A03

Adv

ALA

OFF

ON

ALA

DISC

A+D

P.68

Alarm delay A03

Adv

5

0-240

P.69

Delay UoM A03

Adv

Sec

Min

Sec

P.70

Alarm activation A04

Adv

ALA

OFF

ON

ALA

DISC

A+D

P.71

Alarm delay A04

Adv

120

0-240

P.72

Delay UoM A04

Adv

Sec

Min

Sec

P.73

Alarm activation A05

Adv

A+D

OFF

ON

ALA

DISC

A+D

P.74

Alarm delay A05

Adv

0

0-240

P.75

Delay UoM A05

Adv

Sec

Min

Sec

P.76

Alarm activation A06

Adv

A+D

OFF

ON

ALA

DISC

A+D

P.77

Alarm delay A06

Adv

0

0-240

2014-AT3-5-01-ANG.indd 10

20/03/14 11:46

Summary of Contents for ALPTEC 3.2

Page 1: ...stalled by qualified personnel complying to current standards to avoid damages or safety hazards Before any maintenance operation on the device remove all the voltages from measuring and supply inputs...

Page 2: ...ble 2 level password protection for settings Backup copy of original commissioning settings Built in temperature sensor Tool less panel mount Display indications Introduction The ALPTEC automatic powe...

Page 3: ...en when the power supply voltage is removed When the power returns the original state of the steps is restored Select step Change step status MAN mode icon Connected steps Tot kvar inserited in MAN Ma...

Page 4: ...stortion THD of plant voltage VH02 VH1 5 voltage harmonic content from 2 nd up to 15 th order Current THD THDI Total harmonic distortion THD of plant current IH02 IH15 Current harmonic content from 2...

Page 5: ...ured through the front optical port using the IR USB code CX01 programming dongle or with the IR WiFi code CX02 dongle This programming port has the following advantages You can configure and service...

Page 6: ...tom menu non available on this version EXIT Exits without saving cancel SAVE Exits saving modifications Press MAN AUT to access the submenu When you are in a submenu the main display shows the code of...

Page 7: ...acters available The parameter code can be used however as a reference Note The parameters shown in the table with a shaded background are essential to the operation of the system thus they represent...

Page 8: ...With small values of P 10 the regulation is fast more accurate around the setpoint but with more step swithchings With high values instead we ll have slower reactions of the regulation with fewer swit...

Page 9: ...vanced level access P 24 Number of phases of the power correction panel P 25 Enables the measurement of the actual power of the step performed each time they are switched in The measure is calculated...

Page 10: ...ctually inserted with reference to the total reactive power installed in the panel Curr act nom Percentage of actual plant current with reference to the maximum current of the CT Delta kvar bar graph...

Page 11: ...rm activation A12 Adv ALA OFF ON ALA DISC A D P 95 Alarm delay A12 Adv 0 0 240 P 96 Delay UoM A12 Adv Sec Min Sec P 97 Alarm activation A13 Adv A D OFF ON ALA DISC A D P 98 Alarm delay A13 Adv 5 0 240...

Page 12: ...er than minimum measuring range The plent should be off load A04 Current too high The current flowing in the current inputs is higher than maximum measuring range A05 Voltage too low The measured volt...

Page 13: ...o execute the selected command The unit will prompt for a confirmation OK Press once again MAN AUT to confirm or MODE to cancel The following table lists the possible commands COD COMMAND DESCRIPTION...

Page 14: ...N P 24 1PH NOTES IMPORTANT The polarity of the current voltage input is indifferent Configuration with MV measurement and correction on LV side Typical diagram do not represent the internal connexion...

Page 15: ...rrent Ie 1 AA or 5 AA Measuring range for 5A scale 0 025 6AA for 1A scale 0 025 1 2AA Type of input Shunt supplied by an External current transformer low voltage Max 5A Measuring method True RMS Overl...

Page 16: ...0 56 Nm 5 LBin Housing Version Flush mount Material Polycarbonate Degree of protection IP54 on front IP20 terminals Weight 350g Certifications and compliance cULus Pending Reference standards IEC EN...