8. Technical data
Model
e-MOCarz
Capacity
575 [m
3
/h]
Consumption
9 (12 with ionisation module) [W]
Power input
230 - 50/60 [V - Hz]
Dimensions AxBxC
360x385x230 [mm]
Weight
11 [kg]
Cells
1 [n°]
Cones and collars
160, 200, 250 [mm]
Installation
wall, ceiling
Type of alarm
Cause
Operation
Led status
is RED
electrostatic cell dirty
carry out normal maintenance
electrostatic cell not properly clean
if small dirty areas have remained,
washing must be carried out again
electrostatic cell damp
dry the cell thoroughly and particularly
in the zone of the insulators
electrostatic cell not properly rinsed
there may be detergent on the insulators;
the cell must be thoroughly rinsed again
small bodies trapped between the collection blades
there may be detergent on the insulators;
the cell must be thoroughly rinsed again
electrostatic cell short circuited
due to breakage of an ionisation wire
the wire must be removed
and replaced immediately
electrostatic cell short circuited
due to collection blade being bent
the blade must be straightened
(call a specialised technician)
7.3 Electric circuit alarm signals
The electronic circuit will light up an eventually block of filtration. The causes often can be resolved by a small
operation.
29
ALNOR
®
ventilation systems
is a legally protected trademark and technical patent. All rights reserved.
w
w
w
.al
nor
.com.
pl
User’s manual
e-MOCarz