STD-200-CA1

INSTALLATION MANUAL STD-200-CA1

1- Introducción

Give an extra protection to your capacitor bank with the new 

STD-200-CA1 fire detector unit.
This product has the latest technology in fire detection that 

makes this product a must for the people that requires the 

best protection to their capacitor banks.
The elegant design of the product it suits perfectly with any 

installation, no matter what are the requirements. It has been 

developed using the most innovative technical advances. The 

STD-200-CA1 fire detector unit is based in an optical dark 

chamber, which, thanks to its desing, avoids un wanted air 

flows and facilitates the guidance of the smoke to the sensor. 

The detection principle is based on the Tyndall effect: when 

the  smokes  comes  into  the  optical  chamber,  the  detector 

goes  into,  alarm  status  due  to  the  scattered  light  received 

by the optical sensor. The camera is protected to avoid the 

entrance of dirt and insects. This detector also incorporates 

compensation algorithms which avoid false alarms due to the 

dirtiness of the optical chamber, and it postpones equipment 

maintenance.

2- Installation    

Below is a standard wiring of the detector.

Placement of the detector

Do  not  place  detectors  along  the  walls,  leave  a  minimum 

of  10  cm  from  the  detector  to  the  nearest  wall.  consider 

whether there are elements that may obstruct the movement 

of smoke.

Detector fixation

The  detectors  are  fixed  to  the  connection  base  STD-200-

CA1 by turning the detector in the direction of clockwise. To 

remove it you must rotate in opposite direction.

ENGLISH

The  detectors  have  a  fixation  system  that  prevents  the 

detector  can  be  removed  without  using  a  tool.  To  use  the 

fixation is necessary to cut the tab shown in the picture below.

If  you  want  to  extract  a  detector  that  has  been  blocked,  it 

is necessary to use a screwdriver into the slot by pressing 

the  detector  and  rotating  the  detector  at  the  same  time  in 

opposite direction of clockwise.

3- Test and Maintenance    

Once installed the detectors, the installation must be powered.
In  case  of  any  detector  enabled,  check  that  there  are  no 

environmental  causes  or  artificially  generated,  which  can 

adversely  affect  the  detector  performance  (dust, vapor, air, 

currents, etc.)
the  maintenance  of  the  detectors  must  be  performed  in 

government regulations, checking that in the smoke detectors 

enters smoke inside the camera sensor, and that the detector 

goes into alarm by activating the red LED. In case of using 

aerosols,  read  carefully  the  manufacturer’s  instructions  to 

avoid damaging the detector.
The  maintenance  of  smoke  detectors,  caution  should  be 

exercised  with  dirt  inside  the  camera  sensor,  as  it  could 

generate  false  alarms.  To  clean  the  camera,  do  it  with 

pressure  air.  There  must  be  not  removed  at  any  time  the 

camera or the dome of the detector.

3- Technical features    

Model-Reference

STD-200-CA1

Environmental features

• 

Working Temperature

-10 to 70 ºC

• 

Storage Temperature

-10 to 80 ºC

• 

Relative Humidity

95% without condensation

• 

Protection Index

IP40

Detector Features

• 

Operating voltage

220 VCA

• 

Quiescent current 

consumption

<10µA

• 

Alarm 

current 

consumption

<100mA

Connections features

• 

Terminal 

block 

connection 

2 wire power and 2 wire relay 

signal

• 

Cable type

0.5 mm

to base

Physical features

• 

Height x Ø

70 x Ø 100mm

• 

Material

ABS