Code
Diagnostic Codes/Status of Equipment
Action Required to Clear and Recover
E400
LSOM - Compressor internal overload
tripped
Thermostat demand Y1 is present; but, compressor is not running.
Check power to outdoor unit. Clears the error after current is sensed in
both RUN and START sensors for at least 2 seconds, or after service is
removed; or power reset.
E401
LSOM - Compressor long run cycle or
low system pressure.
Compressor ran more that 18 hours to satisfy a single thermostat de-
mand. Critical Alert. Clears the error after 30 consecutive normal run
cycles or power reset. Also monitors low pressure switch trips.
E402
LSOM - Outdoor unit system pressure
trip.
Discharge or suction pressure out-of-limits, or compressor overloaded.
Clears the error after 4 consecutive normal compressor run cycles.
E403
LSOM - Compressor short-cycling
(Running less than 4 minutes). Out
-
door unit pressure trip.
Compressor runs less than 3 minutes to satisfy a thermostat demand.
Clears the error after 4 consecutive normal run cycles or power reset.
E404
LSOM - Compressor rotor locked.
Compressor short-cycling. (Running
less than 4 minutes.)
Compressor rotor locked up due to run capacitor shore, bearings are
seized, excessive liquid refrigeration, etc. Clears the error after 4 con-
secutive normal run cycles or power reset.
E405
LSOM - Compressor open circuit.
Compressor circuit open (due to power disconnection, open fuse, etc.)
Clears the error after 1 normal compressor run cycle.
E406
LSOM - Compressor open start circuit.
Required amount of current is not passing through Start current trans-
former. Clears the error after current is sensed in START sensor, or
after power reset.
E407
LSOM - Compressor open run circuit.
Required amount of current is not passing through Run current trans-
former. Clears the error after current is sensed in RUN sensor, or 1
normal compressor run cycle, or after power reset.
E408
LSOM - Compressor contactor is
welded.
Compressor runs continuously. Clears the error after 1 normal com-
pressor run cycle or after power reset.
E409
LSOM - Compressor low voltage.
Secondary voltage s below 18VAC. After 10 minutes, operation is
discontinued. Clears the code after voltage is higher than 20VAC for 2
seconds or after power reset.
Summary of Contents for A96US2V
Page 3: ...507404 02 Page 3 of 80 Issue 1448 EXPANDED VIEW Figure 1 ...
Page 31: ...507404 02 Page 31 of 80 Issue 1448 Figure 38 ...
Page 38: ...507404 02 Page 38 of 80 Issue 1448 Figure 56 TRAP DRAIN ASSEMBLY USING 1 2 PVC or 3 4 PVC ...
Page 41: ...507404 02 Page 41 of 80 Issue 1448 Table 9 ...
Page 45: ...507404 02 Page 45 of 80 Issue 1448 ...
Page 47: ...507404 02 Page 47 of 80 Issue 1448 Integrated Control Figure 56 ...
Page 78: ...507404 02 Page 78 of 80 Issue 1448 Start Up Performance Check List UNIT SET UP ...
Page 79: ...507404 02 Page 79 of 80 Issue 1448 UNIT OPERATION Heating Mode Cooling Mode ...