507404-02
Page 53 of 80
Issue 1448
HEATING
1
Heating Speed Dip
Switch Setting
First Stage heating Speed - cfm
Second Stage Heating Speed-cfm
+24%
1210
1300
+18%
1150
1240
+12%
1090
1175
+6%
1035
1115
Fauctory Default
975
1050
-6%
915
990
-12%
860
925
-18%
800
860
COOLING
1
Cooling Speed DIP
Switch Settings
First Stage Cooling Speed -cfm
Second Stage Cooling Speed-cfm
Low Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
605
745
855
965
880
1045
1210
1375
Factory
550
675
775
875
800
950
1100
1250
-
495
610
700
785
720
855
990
1125
A96US2V090C12S BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.c. (Heating) and 0 through 1.0 in. w.c. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed Dip
Switch Setting
First Stage heating Speed - cfm
Second Stage Heating Speed-cfm
+24%
1425
1580
+18%
1355
1505
+12%
1290
1430
+6%
1220
1350
Fauctory Default
1150
1275
-6%
1080
1200
-12%
1010
1120
-18%
945
1045
COOLING
1
Cooling Speed DIP
Switch Settings
First Stage Cooling Speed -cfm
Second Stage Cooling Speed-cfm
Low Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
770
935
1075
1240
1100
1320
1540
1760
Factory
700
850
975
1125
1000
1200
1400
1600
-
630
765
880
1015
900
1080
1260
1440
A96US2V090C16S BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.c. (Heating) and 0 through 1.0 in. w.c. (Cooling) External Static Pressure Range
1
Cooling and Heating speed are based on a combination of DIP switch setting on the furnace control. Refer to installation instructon for specific DIP
Switch settings
2
Factory default setting
NOTES:
The effect of static pressure is included in air volumes shown.
First stage Cool (two stage air conditioning units only) is approximately 70% of the same second stage COOL speed position
Continous Fan Only speed approximately 50% of the selected second stage cooling speed - minimum 500cfm.
1
Cooling and Heating speed are based on a combination of DIP switch setting on the furnace control. Refer to installation instructon for specific DIP
Switch settings
2
Factory default setting
NOTES:
The effect of static pressure is included in air volumes shown.
First stage Cool (two stage air conditioning units only) is approximately 70% of the same second stage COOL speed position
Continous Fan Only speed approximately 50% of the selected second stage cooling speed - minimum 500cfm.
Summary of Contents for A96US2V
Page 3: ...507404 02 Page 3 of 80 Issue 1448 EXPANDED VIEW Figure 1 ...
Page 31: ...507404 02 Page 31 of 80 Issue 1448 Figure 38 ...
Page 38: ...507404 02 Page 38 of 80 Issue 1448 Figure 56 TRAP DRAIN ASSEMBLY USING 1 2 PVC or 3 4 PVC ...
Page 41: ...507404 02 Page 41 of 80 Issue 1448 Table 9 ...
Page 45: ...507404 02 Page 45 of 80 Issue 1448 ...
Page 47: ...507404 02 Page 47 of 80 Issue 1448 Integrated Control Figure 56 ...
Page 78: ...507404 02 Page 78 of 80 Issue 1448 Start Up Performance Check List UNIT SET UP ...
Page 79: ...507404 02 Page 79 of 80 Issue 1448 UNIT OPERATION Heating Mode Cooling Mode ...