SwitchBlade Power Supply Unit

C613-04028-01 REV B

Also plug the power cord into an outlet that can supply a voltage of 90-
264V AC.

Make sure the Standby switch is in the Run position.

Figure 3: AC power connectors.

9.

Apply DC power to the chassis (for DC models)

Read the 

Safety and Statutory Information

 booklet before connecting a DC 

power supply. A copy of the safety booklet is included with each PSU. A 
PDF version is included on the Documentation and Tools CD-ROM 
shipped with every switch controller and every chassis, or can be 
downloaded from www.alliedtelesyn.co.nz/support/switchblade/.

Only trained and qualified personnel should connect a DC power supply. Due 
to exposed terminals, DC powered switches should only be installed in 
Restricted Access Areas.

DC supply cable specifications:

Number of wires (cores): 3 (only 2 wires are required if the switch is 
ground bonded via the separate ground terminal on the chassis’s rear 
panel)

Minimum size: 3.3 mm

2

 (12 AWG)

Minimum  cable  rating:  600V, 90 degrees Celsius

DC power supply specifications:

48 V DC (36-59 V DC is acceptable)

Either positive grounded or negative grounded

Circuit protection:

Use a 20 Amp circuit breaker

To connect the DC supply:

Ensure that the supply cable is not live.

a) Strip the supply cable wires to expose 8mm (0.31 in.) of bare conductor

b) If using 3 wires, on the chassis’s rear panel, connect the

 

ground wire to 

the ground terminal for the corresponding PSU (The terminals can be 

AC INPUT

100-240V

8.0-4.0A
50-60Hz

AC INPUT

100-240V

8.0-4.0A
50-60Hz

AC INPUT

100-240V

8.0-4.0A
50-60Hz

RESET

RUN

STANDBY

Switch

Blade

4000

Summary of Contents for SWITCHBLADE 4000

Page 1: ...SWITCHBLADE POWER SUPPLY UNIT QUICK INSTALL GUIDE...

Page 2: ...changes in specifications and other information contained in this document without prior written notice The information provided herein is subject to change without notice In no event shall Allied Tel...

Page 3: ...r supply unit One IEC power cord AC models only One Power Supply Unit Quick Install Guide One Safety and Statutory Information booklet One warranty card Related items that can be purchased separately...

Page 4: ...yn co nz support switchblade 2 Gather the tools and equipment you will need To loosen or secure the PSU s mounting screws you will need a Phillips 2 screwdriver 3 Choose a PSU bay PSU bays should be f...

Page 5: ...our Phillips screws until they disengage from the chassis Using the PSU s handle pull the PSU out of the chassis 6 Insert the PSU Slowly and carefully slide the PSU into the chassis see Figure 2 on pa...

Page 6: ...wered switches should only be installed in Restricted Access Areas DC supply cable specifications Number of wires cores 3 only 2 wires are required if the switch is ground bonded via the separate grou...

Page 7: ...applied to the cable f Ensure that the circuit breaker is in the Off position g Connect the supply cable wires to the circuit breaker h Energise the circuit breaker i Make sure the Standby switch on...

Page 8: ...tions as well as tools for managing the switch The SwitchBlade Safety and Statutory Information Booklet which provides safety and statutory information for the SwitchBlade and its accessories The Swit...

Reviews: