K-Series Packaged Gas / Electric 7.5 to 12.5 Ton / Page 34
ELECTRICAL DATA
10 TON
10 TON STANDARD EFFICIENCY (R-410A)
KGA/KGB120S4
1
Voltage - 60hz
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Compressor 1
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Compressor 2
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Outdoor Fan
Motors (2)
Full Load Amps
2.4
1.3
1
(total)
(4.8)
(2.6)
(2)
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
15
15
20
Indoor Blower
Motor
Horsepower
2
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
2
Maximum
Overcurrent
Protection
Unit Only
50
50
60
30
30
35
20
20
25
With (1) 0.33 HP
Power Exhaust
50
60
70
30
30
35
20
20
25
3
Minimum
Circuit
Ampacity
Unit Only
43
46
53
24
26
29
16
18
20
With (1) 0.33 HP
Power Exhaust
46
49
56
26
27
30
17
19
21
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
10 TON HIGH EFFICIENCY (R-410A)
KGA120H4
1
Voltage - 60hz
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Compressor 1
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Compressor 2
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Outdoor Fan
Motors (2)
Full Load Amps
2.4
1.3
1
(total)
(4.8)
(2.6)
(2)
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
15
15
20
Indoor Blower
Motor
Horsepower
2
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
2
Maximum
Overcurrent
Protection
Unit Only
50
50
60
30
30
35
20
20
25
With (1) 0.33 HP
Power Exhaust
50
60
70
30
30
35
20
20
25
3
Minimum
Circuit
Ampacity
Unit Only
43
46
53
24
26
29
16
18
20
With (1) 0.33 HP
Power Exhaust
46
49
56
26
27
30
17
19
21
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.