K-Series Packaged Gas / Electric 7.5 to 12.5 Ton / Page 19
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
8.5 TON STANDARD EFFICIENCY KGB102S4B (1ST STAGE) - CONSTANT AIR VOLUME
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
63°F
2720
57.3
2.49
0.63 0.76 0.91
53.8
2.78
0.63 0.77 0.93
50.0
3.10
0.63 0.79 0.96
46.1
3.49
0.63
0.81
0.99
3400
61.1
2.51
0.67 0.83 0.99
57.4
2.79
0.67 0.85 1.00
53.3
3.11
0.68 0.87 1.00
49.0
3.49
0.69
0.90
1.00
4080
63.9
2.51
0.71 0.90 1.00
59.9
2.79
0.72 0.92 1.00
55.7
3.12
0.73 0.95 1.00
51.1
3.50
0.75
0.98
1.00
67°F
2720
60.9
2.50
0.50 0.61 0.73
57.2
2.79
0.50 0.61 0.73
53.4
3.11
0.49 0.61 0.75
49.3
3.49
0.49
0.62
0.76
3400
64.9
2.50
0.53 0.65 0.79
61.0
2.79
0.52 0.65 0.81
56.8
3.12
0.52 0.66 0.83
52.4
3.50
0.52
0.67
0.86
4080
67.8
2.52
0.55 0.69 0.86
63.7
2.81
0.55 0.69 0.88
59.4
3.13
0.55 0.71 0.91
54.7
3.51
0.55
0.73
0.94
71°F
2720
64.2
2.51
0.39 0.49 0.59
60.5
2.80
0.38 0.49 0.59
56.5
3.12
0.37 0.48 0.59
52.4
3.51
0.35
0.48
0.60
3400
68.4
2.52
0.40 0.52 0.63
64.4
2.80
0.39 0.52 0.63
60.1
3.13
0.38 0.51 0.64
55.6
3.52
0.37
0.51
0.65
4080
71.4
2.53
0.41 0.54 0.66
67.3
2.82
0.41 0.54 0.67
62.8
3.14
0.40 0.54 0.69
58.0
3.52
0.39
0.54
0.70
8.5 TON STANDARD EFFICIENCY KGB102S4B (2ND STAGE) - CONSTANT AIR VOLUME
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
63°F
2720
95.0
6.52
0.67 0.82 0.96
87.4
7.34
0.67 0.83 0.99
79.3
8.28
0.68 0.85 1.00
70.8
9.42
0.69
0.88
1.00
3400
101.3
6.54
0.72 0.89 1.00
93.1
7.35
0.73 0.91 1.00
84.6
8.30
0.74 0.94 1.00
75.4
9.43
0.76
0.98
1.00
4080
105.8
6.55
0.77 0.96 1.00
97.1
7.37
0.78 0.98 1.00
88.4
8.31
0.80 1.00 1.00
79.8
9.44
0.83
1.00
1.00
67°F
2720
101.4
6.54
0.52 0.65 0.78
93.5
7.34
0.52 0.66 0.80
85.3
8.30
0.50 0.66 0.82
76.5
9.43
0.50
0.67
0.84
3400
108.0
6.56
0.55 0.70 0.85
99.6
7.37
0.55 0.71 0.87
90.8
8.31
0.55 0.72 0.90
81.5
9.43
0.54
0.74
0.94
4080
112.7
6.57
0.58 0.75 0.92 103.9
7.37
0.58 0.76 0.95
94.8
8.33
0.58 0.78 0.98
85.1
9.46
0.59
0.81
1.00
71°F
2720
107.3
6.56
0.38 0.52 0.63
99.5
7.37
0.37 0.51 0.64
91.0
8.31
0.35 0.50 0.64
82.1
9.45
0.33
0.49
0.65
3400
114.3
6.58
0.40 0.54 0.68 105.7
7.39
0.39 0.54 0.69
96.6
8.34
0.37 0.54 0.70
87.2
9.46
0.35
0.54
0.72
4080
119.3
6.60
0.41 0.58 0.73 110.2
7.40
0.40 0.58 0.74 100.8
8.36
0.39 0.58 0.76
90.9
9.49
0.38
0.59
0.78
8.5 TON HIGH EFFICIENCY KGA102H4B (1ST STAGE) - CONSTANT AIR VOLUME
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
63°F
2720
53.6
2.17
0.61 0.76 0.95
50.7
2.45
0.62 0.78 0.98
47.7
2.77
0.62
0.8
1.00
44.6
3.13
0.63
0.83
1.00
3400
56.5
2.18
0.66 0.87 1.00
53.5
2.46
0.66 0.89 1.00
50.3
2.78
0.68 0.93 1.00
47.1
3.13
0.70
0.97
1.00
4080
58.7
2.18
0.72 0.97 1.00
55.6
2.47
0.74 1.00 1.00
52.4
2.78
0.76 1.00 1.00
49.4
3.14
0.78
1.00
1.00
67°F
2720
57.0
2.18
0.48 0.59 0.71
54.1
2.46
0.49 0.60 0.73
51.0
2.78
0.48 0.61 0.75
47.7
3.14
0.48
0.61
0.78
3400
60.0
2.19
0.51 0.64 0.82
56.8
2.47
0.51 0.64 0.84
53.6
2.78
0.52 0.66 0.88
50.1
3.14
0.52
0.67
0.92
4080
62.2
2.19
0.54 0.69 0.93
58.9
2.48
0.55 0.71 0.96
55.5
2.79
0.55 0.73 0.99
51.8
3.14
0.55
0.76
1.00
71°F
2720
60.4
2.19
0.37 0.47 0.57
57.5
2.47
0.37 0.48 0.58
54.2
2.78
0.36 0.47 0.59
50.8
3.14
0.35
0.47
0.59
3400
63.5
2.20
0.38 0.50 0.62
60.2
2.48
0.38 0.51 0.63
56.8
2.79
0.37 0.51 0.64
53.3
3.15
0.37
0.52
0.65
4080
65.6
2.20
0.39 0.53 0.67
62.3
2.49
0.40 0.54 0.68
58.9
2.80
0.39 0.54 0.70
55.0
3.15
0.39
0.55
0.73
8.5 TON HIGH EFFICIENCY KGA102H4B (2ND STAGE) - CONSTANT AIR VOLUME
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
63°F
2720
98.9
5.54
0.70 0.85 1.00
92.5
6.27
0.71 0.87 1.00
85.7
7.10
0.71 0.90 1.00
78.6
8.09
0.73
0.94
1.00
3400
104.2
5.56
0.76 0.95 1.00
97.5
6.27
0.77 0.98 1.00
90.4
7.11
0.79 1.00 1.00
83.6
8.08
0.82
1.00
1.00
4080
108.6
5.56
0.82 1.00 1.00 102.3
6.28
0.84 1.00 1.00
95.9
7.12
0.87 1.00 1.00
88.9
8.08
0.91
1.00
1.00
67°F
2720
105.6
5.56
0.53 0.67 0.81
98.9
6.28
0.53 0.68 0.83
91.8
7.11
0.54 0.69 0.87
84.4
8.08
0.55
0.71
0.90
3400
110.9
5.57
0.58 0.74 0.91 103.8
6.29
0.59 0.75 0.94
96.4
7.12
0.59 0.77 0.97
88.5
8.08
0.59
0.79
1.00
4080
114.8
5.58
0.61 0.80 0.99 107.2
6.30
0.62 0.82 1.00
99.6
7.12
0.63 0.85 1.00
91.5
8.08
0.63
0.88
1.00
71°F
2720
112.1
5.57
0.40 0.53 0.65 105.2
6.29
0.39 0.53 0.66
98.1
7.12
0.38 0.53 0.67
90.3
8.08
0.38
0.54
0.69
3400
117.6
5.59
0.42 0.57 0.72 110.4
6.30
0.41 0.58 0.73 102.7
7.12
0.41 0.58 0.75
94.3
8.08
0.40
0.59
0.77
4080
121.7
5.60
0.44 0.61 0.77 113.9
6.31
0.43 0.61 0.79 105.9
7.13
0.42 0.62 0.83
97.4
8.08
0.43
0.63
0.86