Elevated Pad, in. [mm]
Description
20-30
40-60
(F-speed)
40-60
(V-speed)
80-100
A
Height of elevated pad above floor
(maximum)
8 [203]
8 [203]
8 [203]
8 [203]
B
Distance between reinforcing bars
(maximum)
12 [305]
12 [305]
12 [305]
12 [305]
C
Length of reinforcing bar extending in-
to existing floor (minimum)
2.5 [64]
2.5 [64]
2.5 [64]
2.5 [64]
D
Total depth of foundation (concrete
plus 6 in. [152 mm] fill) (minimum)
8 [203]
8 [203]
12 [305]
15 [381]
E
Required thickness of existing floor
(minimum)
4 [102]
4 [102]
6 [152]
6 [152]
Table 16
Tie-in to Existing Floor (refer to
Table
17
)
CHM2390N_SVG
1
2
B
C
D
A
4
5
3
1.
Existing Floor
2.
3500 PSI (minimum) Concrete
3.
Reinforcing Bar
4.
Perimeter Reinforcing Bar
5.
Compacted Fill (minimum 6 in. [152 mm])
Figure 18
Tie-in to Existing Floor, in. [mm]
Description
20-30
40-60
(F-speed)
40-60
(V-speed)
80-100
A
Required thickness of existing floor
(minimum)
4 [102]
4 [102]
6 [152]
6 [152]
Table 17
continues...