SLC 500 Thermocouple/mV Analog Input Module
5
Publication 1746-5.23
Input Ranges
The following tables define thermocouple types and associated temperature
ranges and the millivolt analog input signal ranges that each of the module’s
input channels will support. To determine the practical temperature range of your
thermocouple, refer to the specifications in Appendix A of the SLC 500
Thermocouple/mV Analog Input Module User Manual, publication 1746-6.22.
Thermocouple Temperature Ranges
Millivolt Input Ranges
Each input channel is individually configured for a specific input device. Each
channel detects and indicates:
• open-circuit
• over-range
• under-range
Type
°C Temperature Range
°F Temperature Range
J
-210 °C to 760 °C
-346 °F to 1400 °F
K
-270 °C to 1370 °C
-454 °F to 2498 °F
T
-270 °C to 400 °C
-454 °F to 752 °F
B
300 °C to 1820 °C
572 °C to 3308 °F
E
-270 °C to 1000 °C
-454 °F to 1832 °F
R
0 °C to 1768 °C
32 °F to 3214 °F
S
0 °C to 1768 °C
32 °F to 3214 °F
N
0 °C to 1300 °C
32 °F to 2372 °F
CJC Sensor
-25 °C to 105 °C
-13 °F to 221 °F
-50 to +50 mV
-100 to +100 mV
Spare Allen-Bradley Parts