8
Rockwell Automation Publication 1732IL-IN001B-EN-P - April 2019
ArmorBlock 16-Channel IO-Link Hubs
Specifications
This table includes a subset of specifications for the IO-Link hubs. For a complete list of specifications, see the 1732 ArmorBlock I/O Modules
Selection Guide, publication
.
Attribute
1732IL-IB16M12
1732IL-10X6M12
1732IL-16CFGM12M12L
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-20 °C < Ta < +70 °C (-4 °F < Ta < +158 °F)
Temperature, ambient max
70 °C (158 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test dB, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
15 g @ 5…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD Immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±3 kV at 5 kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5
±500V line-line(DM) and ±1 kV line-earth(CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure type rating
Meets IP65/67/69K
(3)
(3)
When sealing caps and cable termination are used. Refer to the 1732 ArmorBlock I/O Modules Selection Guide, publication
for a list of appropriate cables to meet IP rating.
Voltage and current ratings
24V DC, 4.6 mA
24V DC, 5.3 mA
All supply power and/or current ratings
24V DC (SELV/PELV), 100 mA
Isolation voltage
500V DC
Basic
Wiring Category
(1)(2)
(1)
Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication
(2)
Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.
2 - on signal ports
Weight, approx.
380 g (13.40 oz.)
390 g (13.76 oz.)