All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
5
Bulletin 1606 Switched Mode Power Supplies
Fig. 3-5
De-rating requirements for
low input voltages
0
85Vac
10
20
30
40
50
60W
Input Voltage
A... < +45°C
B... < +60°C
A
B
90Vac
Allowable
Output Power
4. Input Inrush Current
An electronic inrush current circuit limits the input inrush current after turn-on of the input voltage. The inrush current
is input voltage and ambient temperature independent.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush current
max.
8A
peak
8A
peak
8A
peak
between
-40°C
and
+70°C
typ.
6A
peak
6A
peak
6A
peak
between
-40°C
and
+70°C
Inrush energy
max.
0.2A
2
s 0.2A
2
s 0.3A
2
s
between -40°C and +70°C
Fig. 4-1
Input inrush current, typical behavior
Input Voltage
Input Current
Output Voltage
Input:
230Vac
Output:
24V, 2.5A
Ambient: 25°C
Upper curve:
Input current 2A/DIV
Middle curve:
Input voltage 200V/DIV
Lower curve:
Output voltage 5V/DIV
Time basis:
20ms / DIV