All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
20
Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
21.6. Daisy Chaining of Outputs
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.
Fig. 21-3 Daisy chaining of outputs
Fig. 21-4 Using distribution terminals
Power
Supply
+ +
- -
Input
Output
Load
+
-
max 25A!
Power
Supply
+ +
- -
Input
Output
Load
+
-
Distribution
Terminals
Power
Supply
+ +
- -
Input
Output
Power
Supply
+ +
- -
Input
Output
21.7. Inductive and Capacitive Loads