Allen-Bradley Rockwell Automation 1606-XLP60EQT Reference Manual Download Page 21

All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM014A-EN-P — March 2014

21

Bulletin 1606 Switched Mode Power Supplies

21.8. Series Operation

 

Power supplies of the exact same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 
with a potential above 60Vdc are not SELV any more and can be dangerous. 
Such voltages must be installed with a protection against touching. Grounding of 
the output is required when the sum of the output voltage exceeds 60Vdc. 
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals. Keep an installation clearance of 15mm (left / 
right) between two power supplies and do not install the power supplies on 
top of each other. Do not use power supplies in series in mounting 
orientations other than the standard mounting orientation (input terminals on the bottom and output terminals on 
top of the unit). Be aware that leakage current, EMI, inrush current and harmonics will increase when using multiple 
power supplies in series. 

Earth

Unit A

AC

DC

Unit B

AC

DC

-

+

-

+

Load

+

-

21.9. Operation on Two Phases

 

2

40V 

+10%

 max.

Fuse

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

The power supply can also be used on two-phases of a three-phase-system. 
A phase-to-phase connection is allowed as long as the supplying voltage is 
below 240V

+10%

. Use a fuse or a circuit breaker to protect the N input. The 

N input is not internally protected and is in this case connected to a hot 
wire. Appropriate fuses or circuit breakers are specified in section 21.4 
“External Input Protection”. 

 

21.10. Use Without PE on the Input

 

From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2. 
Please contact RA if you don't intend to use the PE terminal. A different marking of the front foil is then required.  

Grounding of the input is beneficial for a high EMI immunity: symmetrical spikes or fast transients on the input side 
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on 
the output side caused by the input is much smaller than if you're not connecting this terminal to ground. 

 

Fig. 21-5

   Grounded input 

 

Fig. 21-6

   Ungrounded input 

 

Surge

Y

X

L

N

Ground

Power Supply

+

-

 

 

Surge

X

L

N

Power Supply

+

-

24V

Spike

Summary of Contents for Rockwell Automation 1606-XLP60EQT

Page 1: ...2 Use in a Tightly Sealed Enclosure 22 21 13 Mounting Orientations 23 Bulletin 1606 Switched Mode Power Supplies Catalog Number 1606 XLP60EQT Index PE and symbol PE is the abbreviation for Protective...

Page 2: ...or exposed to a critical industrial environment This series of power supplies offers output voltages from 5 to 56Vdc and power ratings from 15W to 120W Principal characteristics of the 1606 XLP60EQT a...

Page 3: ...signed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearanc...

Page 4: ...5A see Fig 3 4 Crest factor typ 3 4 3 7 4 0 at 24V 2 5A Start up delay typ 170ms 110ms 90ms see Fig 3 2 Rise time typ 50ms 50ms 60ms at 24V 2 5A 0mF see Fig 3 2 120ms 110ms 140ms at 24V 2 5A 2 5mF Tu...

Page 5: ...ter turn on of the input voltage The inrush current is input voltage and ambient temperature independent The charging current into EMI suppression capacitors is disregarded in the first microseconds a...

Page 6: ...mum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances There is no guarantee this value will be achieved The typical value is about 28 6V Fig 5 1 Outpu...

Page 7: ...ld up Time Zero Transition Output Voltage Input Voltage 7 DC Input The power supply can also be supplied from a DC source Use a battery or similar DC source For other sources contact RA Connect the po...

Page 8: ...1 25A half load typ 8 6W 7 8W 6 4W at 24V 2 5A full load Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 0 82 86 90 80 92 2 5A 0 5 1 5 2 0 Outpu...

Page 9: ...sh Limiter Power Converter Output Voltage Regulator Output Filter VOUT DC on PE 10 Front Side and User Elements Fig 10 1 Front side A Output Terminals Screw terminals Dual terminals for the negative a...

Page 10: ...olytic capacitors has been reduced AC 100V AC 120V AC 230V Lifetime expectancy 50 000h 66 000h 90 000h at 24V 2 5A and 40 C 122 000h 132 000h 104 000h at 24V 1 25A and 40 C 142 000h 188 000h 255 000h...

Page 11: ...A Voltage interruptions EN 61000 4 11 0Vac 5000ms Criterion C Input voltage swells RA internal standard 300Vac 500ms Criterion A Powerful transients VDE 0160 over entire load range 750V 1 3ms Criteri...

Page 12: ...e Fig 14 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 4W 1000m or 5 C 1000m 2000m 6500ft see Fig 14 2 Over voltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes...

Page 13: ...tion protection 2 5mm in diameter e g screws small parts Over temperature protection Not included Input transient protection MOV Metal Oxide Varistor Internal input fuse T3 15A H B C not user replacea...

Page 14: ...down Connect all phase terminals together as well as all output poles before conducting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric stre...

Page 15: ...ED E168663 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 NEC Class 2 NEC CLASS 2 Listed as Limited Power Source LPS in the UL 60950 1 UL report Acc...

Page 16: ...ch 2014 Bulletin 1606 Switched Mode Power Supplies 19 Physical Dimensions and Weight Weight 250g 0 55lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The D...

Page 17: ...tends the hold up time after turn off of the AC power In times when the power supply provides sufficient voltages the buffer module stores energy in integrated electrolytic capacitors In case of mains...

Page 18: ...n before such an event the built in large sized output capacitors inside the power supply can deliver extra current Discharging this capacitor causes a voltage dip on the output The following two exam...

Page 19: ...al regulations might apply If an external fuse is necessary or utilized minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker A minimum value of 6A B or 3A C Cha...

Page 20: ...next is allowed as long as the average output current through one terminal pin does not exceed 25A If the current is higher use a separate distribution terminal block Fig 21 3 Daisy chaining of output...

Page 21: ...EMI inrush current and harmonics will increase when using multiple power supplies in series Earth Unit A AC DC Unit B AC DC Load 21 9 Operation on Two Phases 240V 10 max Fuse L2 L1 L3 L N PE Power Sup...

Page 22: ...tempts 21 12 Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure the temperature inside the enclosure will be higher than outside In such situations the...

Page 23: ...put current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 21 7 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Power...

Page 24: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Reviews: