8
ProcessLogix Hardware
Publication 1757-5.1 - August 1999
Connect Power
1.
Use #14 AWG 75
°
C copper wire.
2.
Tighten terminals to a torque of 7 inch-pounds.
3.
Connect L1 for the high side of line power.
4.
Connect L2 for the low side of line power.
1.
Remove the protective label from the top of the power supply.
2.
Apply power by toggling the switch on the front of the power supply from
OFF to ON.
ATTENTION
!
Turn off power lines before connecting power. Failure to
do so could cause injury to personnel and/or damage to
equipment.
IMPORTANT
Make sure you mount the chassis and complete work on the
panel before you remove the protective label. The label protects
the power supply from metal shavings falling inside the power
supply and damaging it during operation.