Rockwell Automation Publication 20D-RN047A-EN-P - October 2019
9
5.
Click
Browse
and navigate to the flash file located in:
C:\ Program Files\ControlFLASH\0001\0078\004C
Figure 4 - Send File Screen
6.
In the Select File to Send window list, click on the ‘700S2ap30_01.bin’ file.
Then click
Open
. This file name now appears in the Filename box in the
Send File screen.
7.
In the Protocol box, select “Xmodem.”
8.
Click
Send
.
A dialog box appears and reports the progress of the update. When it is
complete, the message “Flash Complete” appears. Press any key to
continue.
.
9.
Press the
Enter
key to return to the main menu.
Important
Keep the device powered for 15 seconds after the operation has completed or until the
adapter MOD status indicator starts flashing green.
TIP
To cancel the flash update at any time, press
CTRL-X
.