English-2
•
Mount the drive upright on a flat, vertical and level surface.
•
Protect the cooling fan by avoiding dust or metallic particles.
•
Do not expose to a corrosive atmosphere.
•
Protect from moisture and direct sunlight.
Minimum Mounting Clearances
See page 21 for mounting dimensions.
Ambient Operating Temperatures
Mounting Considerations
Frame
Screw Size
Screw Torque
DIN Rail
B
M4 (#8-32)
1.56-1.96 N-m (14-17 lb.-in.)
35 mm
C
M5 (#10-24)
2.45-2.94 N-m (22-26 lb.-in.)
–
Ambient Temperature
Enclosure Rating
Minimum Mounting
Clearances
Minimum
Maximum
-10°C (14°F)
40°C (104°F)
IP 20/Open Type
Use Mounting Option A
IP 30/NEMA 1/UL Type 1
(1)
(1)
Rating requires installation of the PowerFlex 40P IP 30/NEMA 1/UL Type 1 option kit.
Use Mounting Option B
50°C (122°F) IP 20/Open Type
Use Mounting Option B
25 mm
(1.0 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
RUN
REV
FAULT
RUN
REV
FAULT
RUN
REV
FAULT
RUN
REV
FAULT
Mounting Option A
No clearance required
between drives.
Mounting Option B
Closest object that
may restrict air flow
through the drive heat
sink and chassis
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182
http://www.aotewell.com/
All manuals and user guides at all-guides.com