background image

 

English-6

 

Before Applying Power to the Drive 

 

 

1.

 

Confirm that all inputs are connected to the correct terminals and are 
secure.

 

 

2.

 

Verify that AC line power at the disconnect device is within the rated 
value of the drive.

 

 

3.

 

Verify that any digital control power is 24 volts.

 

 

4.

 

Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to 
match your control wiring scheme. See page 5 for location.

 

Important:

 

The default control scheme is Source (SRC). The Stop 
terminal is jumpered (I/O Terminals 01 and 11) to allow 
starting from the keypad. If the control scheme is changed 
to Sink (SNK), the jumper must be removed from I/O 
Terminals 01 and 11 and installed between I/O Terminals 
01 and 04.

 

 

5.

 

Verify that the Stop input is present or the drive will not start.

 

Important:

 

If I/O Terminal 01 is used as a stop input, the jumper 
between I/O Terminals 01 and 11 must be removed.

 

Applying Power to the Drive

 

 

6.

 

Apply AC power and control voltages to the drive.

 

 

7.

 

Familiarize yourself with the integral keypad features (see next page) 
before setting any Program Group parameters.

 

Start, Stop, Direction and Speed Control 

 

Factory default parameter values allow the drive to be controlled from 
the integral keypad. No programming is required to start, stop, change 
direction and control speed directly from the integral keypad.

 

Important:

 

To disable reverse operation, see A095 [Reverse Disable].

If a fault appears on power up, refer to page 11 for an explanation of the 
fault code. For complete troubleshooting information, refer to the 
PowerFlex 4 

 

User Manual

 

 on the CD supplied with the drive.

 

Prepare For Drive Start-Up

!

 

ATTENTION:  

 

Power must be applied to the drive to perform the 

following start-up procedures. Some of the voltages present are at 
incoming line potential. To avoid electric shock hazard or damage to 
equipment, only qualified service personnel should perform the 
following procedure. Thoroughly read and understand the procedure 
before beginning. If an event does not occur while performing this 
procedure, 

 

Do Not Proceed

 

 

Remove All Power

 

 including user 

supplied control voltages. User supplied voltages may exist even when 
main AC power is not applied to the drive. Correct the malfunction 
before continuing.

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for PowerFlex 4

Page 1: ...2 Auto Rstrt Tries A094 Start At PowerUp is used in an inappropriate application Do not use this function without considering applicable local national and international codes standards regulations or...

Page 2: ...56 1 96 Nm 14 17 lb in AmbientTemperature Enclosure Rating Minimum Mounting Clearances Minimum Maximum 10 C 14 F 40 C 104 F IP 20 Open Type Use Mounting Option A IP 30 NEMA 1 UL Type 1 1 1 Rating requ...

Page 3: ...Efficiency 97 5 Typical Digital Control Inputs Input Current 6mA Analog Control Inputs SRC Source Mode 18 24V ON 0 6V OFF SNK Sink Mode 0 6V ON 18 24V OFF 4 20mA Analog 250 ohm input impedance 0 10V D...

Page 4: ...endations Input Power Condition Corrective Action Low Line Impedance less than 1 line reactance Install Line Reactor 2 or Isolation Transformer Greater than 120 kVA supply transformer Line has power f...

Page 5: ...0 ohm P038 16 RS485 DSI Shield Terminal should be connected to safety ground PE when using the RS485 DSI communications port 3 Only one analog frequency source may be connected at a time If more than...

Page 6: ...ny Program Group parameters Start Stop Direction and Speed Control Factory default parameter values allow the drive to be controlled from the integral keypad No programming is required to start stop c...

Page 7: ...gramming menu Cancel a change to a parameter value and exit Program Mode Select Advance one step in programming menu Select a digit when viewing parameter value Up Arrow Down Arrow Scroll through grou...

Page 8: ...parameters that are in the group 7 Press Enter or Sel to view the value of a parameter If you do not want to edit the value press Esc to return to the parameter number 8 Press Enter or Sel to enter p...

Page 9: ...control When in three wire control I O Terminal 01 is controlled by P037 Stop Mode 1 Stop input also clears active fault P038 Speed Reference 0 5 0 Drive Potentiometer 1 Internal Freq 2 0 10V Input R...

Page 10: ...Mechanical 3 Both 1 A098 SW Current Trip 0 0 Drive Amps 2 0 1 Amps 0 0 Disabled A099 Process Factor 0 1 999 9 0 1 30 0 A100 Fault Clear 0 2 0 Ready 1 Reset Active Fault 2 Clear Fault Queue 0 A101 Pro...

Page 11: ...urrent Limit F7 Motor Overload 1 An excessive motor load exists Reduce load so drive output current does not exceed the current set by parameter P033 Motor OL Current F8 Heatsink OvrTmp 1 Check for bl...

Page 12: ...9 87 4 3 44 168 6 61 2 2 4 9 1 Overall height of drive with IP 30 NEMA 1 UL Type 1 option kit installed 2 Overall height of standard IP 20 Open Type drive Frame 120V AC 1 Phase 240V AC 1 Phase 240V AC...

Reviews: