English-4

 

Power Terminal Block (A Frame Shown)

Power Terminal Block Specifications

Input Power Conditions

 

I/O Terminal Block Specifications

 

Refer to the PowerFlex 4 

 

User Manual

 

 on CD for maximum power and 

control cable length recommendations

 

Power Wiring

 

Power Wire Rating

Recommended Copper Wire

 

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Belden 29501-29507 or equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Shawflex 2ACD/3ACD or equivalent

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

 

Terminal

Description

 

R/L1, S/L2

1-Phase Input

R/L1, S/L2, T/L3

3-Phase Input

U/T1

To Motor U/T1

 

=

 

Switch any two motor leads to 
change forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

BR+, BR-

Dynamic Brake Resistor Connection [0.75 kW (1 HP) ratings and higher]

Safety Ground - PE

 

Frame

Maximum Wire Size 

 

(1)

 

Minimum Wire Size 

 

(1)

 

Torque

 

A

3.3 mm

 

2

 

 (12 AWG)

0.8 mm

 

2

 

 (18 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

B

5.3 mm

 

2

 

 (10 AWG)

1.3 mm

 

2

 

 (16 AWG)

 

(1)

 

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

 

Input Power Condition

Corrective Action

 

Low Line Impedance (less than 1% line reactance)

 

 

Install Line Reactor

 

(2)

 

 

or Isolation Transformer

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Line has frequent power interruptions

Line has intermittent noise spikes in excess of 6000V (lightning)

Phase to ground voltage exceeds 125% of normal line to line voltage

 

 

Remove MOV jumper to ground.

 

 

and Install Isolation Transformer with 
grounded secondary if necessary.

Ungrounded Distribution System

 

(2)

 

Refer to Appendix B of the PowerFlex 4 

 

User Manual

 

 on CD for accessory ordering information.

 

I/O Wiring Recommendations

 

(3)

 

Wire Type(s)

Description

Minimum Insulation Rating

 

Belden 8760/9460
(or equiv.)

0.8 mm

 

2

 

(18AWG), twisted pair, 100% shield with 

drain.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

 

2

 

(18AWG), 3 conductor, shielded for 

remote pot only.

 

(3)

 

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be 
necessary, but is always recommended.

 

Maximum Wire Size 

 

(4)

 

Minimum Wire Size 

 

(4)

 

Torque

 

1.3 mm

 

2

 

 (16 AWG)

0.13 mm

 

2

 

 (26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)

 

(4)

 

Maximum / minimum that the terminal block will accept - these are not recommendations.

All manuals and user guides at all-guides.com

Summary of Contents for PowerFlex 4

Page 1: ...2 Auto Rstrt Tries A094 Start At PowerUp is used in an inappropriate application Do not use this function without considering applicable local national and international codes standards regulations or...

Page 2: ...56 1 96 Nm 14 17 lb in AmbientTemperature Enclosure Rating Minimum Mounting Clearances Minimum Maximum 10 C 14 F 40 C 104 F IP 20 Open Type Use Mounting Option A IP 30 NEMA 1 UL Type 1 1 1 Rating requ...

Page 3: ...Efficiency 97 5 Typical Digital Control Inputs Input Current 6mA Analog Control Inputs SRC Source Mode 18 24V ON 0 6V OFF SNK Sink Mode 0 6V ON 18 24V OFF 4 20mA Analog 250 ohm input impedance 0 10V D...

Page 4: ...endations Input Power Condition Corrective Action Low Line Impedance less than 1 line reactance Install Line Reactor 2 or Isolation Transformer Greater than 120 kVA supply transformer Line has power f...

Page 5: ...0 ohm P038 16 RS485 DSI Shield Terminal should be connected to safety ground PE when using the RS485 DSI communications port 3 Only one analog frequency source may be connected at a time If more than...

Page 6: ...ny Program Group parameters Start Stop Direction and Speed Control Factory default parameter values allow the drive to be controlled from the integral keypad No programming is required to start stop c...

Page 7: ...gramming menu Cancel a change to a parameter value and exit Program Mode Select Advance one step in programming menu Select a digit when viewing parameter value Up Arrow Down Arrow Scroll through grou...

Page 8: ...parameters that are in the group 7 Press Enter or Sel to view the value of a parameter If you do not want to edit the value press Esc to return to the parameter number 8 Press Enter or Sel to enter p...

Page 9: ...control When in three wire control I O Terminal 01 is controlled by P037 Stop Mode 1 Stop input also clears active fault P038 Speed Reference 0 5 0 Drive Potentiometer 1 Internal Freq 2 0 10V Input R...

Page 10: ...Mechanical 3 Both 1 A098 SW Current Trip 0 0 Drive Amps 2 0 1 Amps 0 0 Disabled A099 Process Factor 0 1 999 9 0 1 30 0 A100 Fault Clear 0 2 0 Ready 1 Reset Active Fault 2 Clear Fault Queue 0 A101 Pro...

Page 11: ...urrent Limit F7 Motor Overload 1 An excessive motor load exists Reduce load so drive output current does not exceed the current set by parameter P033 Motor OL Current F8 Heatsink OvrTmp 1 Check for bl...

Page 12: ...9 87 4 3 44 168 6 61 2 2 4 9 1 Overall height of drive with IP 30 NEMA 1 UL Type 1 option kit installed 2 Overall height of standard IP 20 Open Type drive Frame 120V AC 1 Phase 240V AC 1 Phase 240V AC...