English-10
A070
A071
A072
A073
[Preset Freq 0]
(1)
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
0.0/240.0 Hz
0.1 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
(1)
To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.
A078 [Jog Frequency]
0.0/[Maximum Freq]
0.1 Hz
10.0 Hz
A079 [Jog Accel/Decel]
0.1/600.0 Secs
0.1 Secs
10.0 Secs
A080 [DC Brake Time]
0.0/90.0 Secs
0.1 Secs
0.0 Secs
A081 [DC Brake Level]
0.0/(Drive Amps
×
1.8) 0.1 Amps
Amps
×
0.05
A082 [DB Resistor Sel]
0/99
0 = Disabled
1 = 5% Duty Cycle
2 = 100% Duty Cycle
3-99 = % of Duty Cycle
0
A083 [S Curve %]
0/100%
1%
0% (Disabled)
A084 [Start Boost]
1/14
Settings in % of base voltage.
8
7 (5 HP Drives)
Variable Torque
Constant Torque
1 = “30.0”
5 = “0.0 no IR Comp” 10 = “10.0”
2 = “35.0”
6 = “0.0”
11 = “12.5”
3 = “40.0”
7 = “2.5”
12 = “15.0”
4 = “45.0”
8 = “5.0”
13 = “17.5”
9 = “7.5”
14 = “20.0”
A088 [Maximum Voltage]
20/Rated Volts
1 VAC
Rated Volts
A089 [Current Limit]
0.1/(Drive Amps
×
1.8) 0.1 Amps
Amps
×
1.5
A090 [Motor OL Select]
0/2
0 = “No Derate”
1 = “Minimum Derate”
2 = “Maximum Derate”
0
A091 [PWM Frequency]
2.0/16.0 kHz
0.1 kHz
4.0 kHz
A092 [Auto Rstrt Tries]
0/9
1
0
A093 [Auto Rstrt Delay]
0.0/120.0 Secs
0.1 Secs
1.0 Secs
A094 [Start At PowerUp]
0/1
0 = “Disabled”
1 = “Enabled”
0
A095 [Reverse Disable]
0/1
0 = “Reverse Enabled”
1 = “Reverse Disabled”
0
A096 [Flying Start En]
0/1
0 = “Disabled”
1 = “Enabled”
0
A097 [Compensation]
0/3
0 = “Disabled”
1 = “Electrical”
2 = “Mechanical”
3 = “Both”
1
A098 [SW Current Trip]
0.0/(Drive Amps
×
2)
0.1 Amps
0.0 (Disabled)
A099 [Process Factor]
0.1/999.9
0.1
30.0
A100 [Fault Clear]
0/2
0 = “Ready”
1 = “Reset Active Fault”
2 = “Clear Fault Queue”
0
A101 [Program Lock]
0/1
0 = “Unlocked”
1 = “Locked”
0
A102 [Testpoint Sel]
0/FFFF
1 Hex
400
A103 [Comm Data Rate]
(3)
0/5
0 = “1200”
1 = “2400”
2 = “4800”
3 = “9600”
4 = “19.2K”
5 = “38.4K”
3
A104 [Comm Node Addr]
(3)
1/247
1
100
A105 [Comm Loss Action]
0/3
0 = “Fault”
1 = “Coast to Stop”
2 = “Stop”
3 = “Continue Last Speed”
0
A106 [Comm Loss Time]
0.1/60.0
0.1
5.0
A107 [Comm Format]
(3)
0/2
0 = “RTU 8-N-1”
1 = “RTU 8-E-1”
2 = “RTU 8-O-1”
0
A110 [0-10V Analog Input
Low]
0.0/100.0%
0.1%
0.0
A111 [0-10V Analog Input
High]
0.0/100.0%
0.1%
100.0
A112 [4-20mA Analog Input
Low]
0.0/100.0%
0.1%
0.0
A113 [4-20mA Analog Input
High]
0.0/100.0%
0.1%
100.0
A114 [Slip Compensation]
0.0/10.0 Hz
0.1 Hz
2.0 Hz
(3)
Power to drive must be cycled before any changes will affect drive operation.
No.
Parameter
Min/Max
Display/Options
Default
Input State of Digital In 1
(I/O Terminal 05)
Input State of Digital In 2
(I/O Terminal 06)
Frequency Source
Accel / Decel Parameter Used
(2)
0
0
[Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
[Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
[Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
[Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
See the PowerFlex 4 User Manual on CD for more information on parameters.