Publication 1766-RM001A-EN-P - October 2008
Conversion Instructions
249
Clearing S:14 before executing the FRD instruction is shown below:
When the input condition I:0/1 is set (1), a BCD value (transferred from a
4-digit thumbwheel switch for example) is moved from word N7:2 into
the math register. Status word S:14 is then cleared to make certain that
unwanted data is not present when the FRD instruction is executed.
CLR
CLEAR
Dest
S:14
0
FRD
FROM BCD
Source
S:13
00001234
Dest
N7:0
1234
MOV
MOVE
Source
N7:2
4660
Dest
S:13
4660
] [
I:1
0
0001 0010 0011 0100
0000 0100 1101 0010
S:13 and S:14 are
displayed in BCD format.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive