Allen-Bradley Kinetix 5000 Installation Instructions Manual Download Page 3

Kinetix 5000 AC Line Filters     

3

Rockwell Automation Publication 2198-IN003B-EN-P - March 2015

Before You Begin

For general guidelines when laying out your panel and mounting your AC line filter, refer to the 
System Design for Control of Electrical Noise Reference Manual, publication 

GMC-RM001

.

For guidelines specific to your application, refer to your drive-family user manual listed in 
Additional Resources on 

page 8

.

Install the AC Line Filter

Mount the line filter to the cabinet panel with hardware as specified in the table below.

See the System Design for Control of Electrical Noise Reference Manual, publication 

GMC-RM001,

 for proper high-frequency (HF) bonding techniques to improve overall system 

performance.

Wire the AC Line Filter

Wire must be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is 
arbitrary and earth ground connection is required to improve safety and proper operation.

ATTENTION: 

To avoid personal injury or damage to equipment due to hazardous voltages, 

follow these guidelines when installing your AC line filter. NEC and local regulations always 
take precedence:

Disconnect mains power before installation.

Verify that the rated voltage is compatible with the local supply voltage.

Connect the earth ground connection first.

AC Line Filter
Cat. No.

Mounting Bolts

Torque Value 

N•m (lb•in)

2198-DB08-F

M5 (#10-32)

2.0 (17.7)

2198-DB20-F

2198-DB42-F

M6 (1/4x20)

4.5 (39.8)

2198-DB80-F

2198-DB290-F

M10 (3/8x16)

30 (266)

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the values and 
methods provided.
When wiring the line filter for single-phase operation (Kinetix 5500 drives only), do not make 
connections to the L3 terminals. Line and load designations must be observed to meet 
product specifications.

Allen-Bradley Replacements

Summary of Contents for Kinetix 5000

Page 1: ...ns for the AC line filters used with the Kinetix 5000 servo drive families For more information on installing and wiring your Kinetix 5500 or Kinetix 5700 servo drive refer to the drive family user ma...

Page 2: ...ith respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automat...

Page 3: ...rating Phasing of main AC power is arbitrary and earth ground connection is required to improve safety and proper operation ATTENTION To avoid personal injury or damage to equipment due to hazardous...

Page 4: ...rive input power IPD connections for three phase operation Line Load 2198 Pxxx DC bus Power Supply 2198 Hxxx ERSx Servo Drives 2198 H003 ERSx 2198 H008 ERSx 2198 H015 ERSx Servo Drives Mains Contactor...

Page 5: ...que Values N m lb in 2198 H003 ERSx 2198 DB08 F 2 2 Applies to installations with single phase or three phase input power 1 5 6 16 10 7 5 0 30 0 8 7 1 2198 H008 ERSx 2198 H015 ERSx 2198 H025 ERSx 2198...

Page 6: ...198 DB20 F AC Line Filter Dimensions catalog number 2198 DB42 F 6 0 0 24 R3 0 0 12 8 5 0 33 217 8 54 201 7 91 227 8 94 1 2 0 05 93 3 66 115 5 4 55 55 2 16 42 1 65 42 1 65 M5 Dimensions are in mm in 6...

Page 7: ...Line Filter Dimensions catalog number 2198 DB290 F 298 11 73 79 3 11 79 3 11 7 0 0 28 1 2 0 05 312 12 28 94 3 70 190 7 48 M8 Dimensions are in mm in 90 3 54 146 5 75 208 8 19 30 1 18 10 5 0 41 268 10...

Page 8: ...at No Voltage Rating Current Rating A 50 C 122 F Power Loss Rated Current W Leakage Current typ mA Weight approx kg lb Operating Temperature 2198 DB08 F 480V AC 1 three phase 50 60 Hz 1 Tolerance for...

Reviews: