48
Publication 1753-RM002C-EN-P - September 2008
Chapter 4
GuardPLC Controller and GuardPLC I/O Output Channels
Relay Outputs in the
1753-OW8 Module
The information in this section applies to the relay outputs of the
1753-OW8 module.
Test Routines
The modules are automatically tested during operation. These are the
essential test functions.
•
Read back the output signal of the switching amplifiers before
the relays.
•
Test the switching of the relays with positively guided contacts.
•
Test the integrated redundant safety shutdown.
The operating voltage of the entire system is monitored, de-energizing
all outputs at an undervoltage of <13V.
At the 1753-OW8 module, the outputs are equipped with three safety
relays; two relays with positive guided contacts and one MSR type
enabling the outputs to be used in safety shutdowns.
Reaction To Error
If a faulty signal is detected, all contact outputs of the module are set
to the safety (0) state via the safety switches in accordance with the
closed-circuit principle. This is also indicated by the FAULT diagnostic
LED indicator.
Relay Outputs in the 1753-OW8
I/O Bus
WD
L+
T
T
T
8 channels
ERR
RUN
Test
8
1
O1...
3.15 AT
...O8
3.15 AT
Summary of Contents for GuardPLC 1753
Page 4: ...4 Publication 1753 RM002C EN P September 2008 Summary of Changes...
Page 8: ...8 Publication 1753 RM002C EN P September 2008 Table of Contents...
Page 12: ...12 Publication 1753 RM002C EN P September 2008 Preface...
Page 84: ...84 Publication 1753 RM002C EN P September 2008 Chapter 7 GuardPLC Controller Operating System...
Page 106: ...106 Publication 1753 RM002C EN P September 2008 Chapter 9 Configuring Communication...
Page 114: ...114 Publication 1753 RM002C EN P September 2008 Appendix B Use in Central Fire Alarm Systems...
Page 118: ...118 Publication 1753 RM002C EN P September 2008 Index...
Page 119: ...Allen Bradley Parts...