GuardPLC Controller and GuardPLC I/O Module Input Channels
Chapter
3
Analog Inputs
The items listed in the following section apply to all of the analog
input channels listed in the Overview on
, if no specific
module is named.
General
In the eight analog input channels available in each module, the
incoming signals are converted into an INTEGER value in 12-bit
resolution. This value can then be used in the application program.
The following input values are possible for the GuardPLC 1800
controller:
IMPORTANT
The safety-related accuracy is the guaranteed accuracy of the
analog input without error reaction of the module. This value
should be taken into account when the safety functions are
configured.
Input Values
Number of
Input Channels
Polarity
Current/Voltage
Value Range In
Application
Accuracy
(5)
(5)
Accuracy is the guaranteed accuracy of the analog input without error reaction of the module. This value must
be considered when safety functions are configured.
8
single-ended
0…10V DC
0…1000
(1)
0…2000
(2)
(1)
With scale factor 1000 selected in RSLogix Guard PLUS! software.
(2)
With scale factor 2000 selected in RSLogix Guard PLUS! software.
2%
8
single-ended
0/4…20 mA
0…500
(1)(3)
0…1000
(1)(4)
0…1000
0…2000
(2)(4)
(3)
By external 250
Ω
shunt.
(4)
By external 500
Ω
shunt.
2%
Summary of Contents for GuardPLC 1753
Page 4: ...4 Publication 1753 RM002C EN P September 2008 Summary of Changes...
Page 8: ...8 Publication 1753 RM002C EN P September 2008 Table of Contents...
Page 12: ...12 Publication 1753 RM002C EN P September 2008 Preface...
Page 84: ...84 Publication 1753 RM002C EN P September 2008 Chapter 7 GuardPLC Controller Operating System...
Page 106: ...106 Publication 1753 RM002C EN P September 2008 Chapter 9 Configuring Communication...
Page 114: ...114 Publication 1753 RM002C EN P September 2008 Appendix B Use in Central Fire Alarm Systems...
Page 118: ...118 Publication 1753 RM002C EN P September 2008 Index...
Page 119: ...Allen Bradley Parts...