FLEX Ex 8 Output and HART Analog Modules
41
Publication
1797-IN003J-EN-P - August 2017
Entity Parameters
CE, CENELEC I/O Entity Parameters (1797-OE8)
Signal output (+ to -) for ch 0 to ch 7
(terminals: 0 and 1; 4 and 5; 8 and 9; 12 and 13; 17 and 18; 21 and 22; 25 and
26; 29 and 30)
CE, CENELEC I/O Entity Parameters (1797-OE8H)
Signal output (+ to -) for ch 0 to ch 7
(terminals: 0 and 1; 4 and 5; 8 and 9; 12 and 13; 17 and 18; 21 and 22; 25 and
26; 29 and 30)
UL, C-UL I/O Entity Parameters (1797-OE8 Only)
If this product has the UL/C-UL mark, it has been designed, evaluated,
tested, and certified to meet the following standards:
• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus
for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations
Protection Group
Allowed
Capacitance
Allowed
Inductance
U
o
= 21V
I
o
= 100 mA
P
o
= 520 mW
EEx ia
IIB
1.27
μ
F
8 mH
IIC
188 nF
2 mH
If concentrated
capacitance and/or
inductance are available,
use the following values.
EEx ia
IIB
295 nF
10 mH
IIC
70 nF
2 mH
Protection
Group
Allowed
Capacitance
Allowed
Capacitance
Internal
Capacitance
Internal
Inductance
U
o
= 21.6V
I
o
= 92 mA
P
o
= 500 mW
EEx ia
IIB
1.18
μ
F
1.18
μ
F
10 nF
0 mH
IIC
164 nF
164 nF
10 nF
0 mH