FLEX Ex 8 Output and HART Analog Modules
17
Publication
1797-IN003J-EN-P - August 2017
1797-OE8 Output Map (Write Words)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
OE FR
Reserved
DD
Ch7
DD
Ch6
DD
Ch5
DD
Ch4
DD
Ch3
DD
Ch2
DD
Ch1
DD
Ch0
1
Channel 0 Output Data
2
Channel 1 Output Data
3
Channel 2 Output Data
4
Channel 3 Output Data
5
Channel 4 Output Data
6
Channel 5 Output Data
7
Channel 6 Output Data
8
Channel 7 Output Data
Where: Res = reserved, Ch = channel
DD = digital data, FR = fault reset
OE = output enable
1797-OE8H Output Map (Write Words)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Res FR
Reserved
DD
Ch7
DD
Ch6
DD
Ch5
DD
Ch4
DD
Ch3
DD
Ch2
DD
Ch1
DD
Ch0
1
Channel 0 Output Data
2
Channel 1 Output Data
3
Channel 2 Output Data
4
Channel 3 Output Data
5
Channel 4 Output Data
6
Channel 5 Output Data
7
Channel 6 Output Data
8
Channel 7 Output Data
Where: Res = reserved, Ch = channel
DD = digital data, FR = fault reset