     E3 Plus EtherNet/IP Adapter

Rockwell Automation Publication 2100-IN090A-EN-P - February 2012

5.

Enter the IP address for the adapter and, if appropriate, enter the host name and an 
adapter description.

6.

Click OK.

Once the IP address you entered shows up in the Request History panel (you may need 
to cycle power to the adapter), this configuration can be permanently assigned to the 
adapter. 

7.

To do so, highlight the adapter in the Relation List panel and click Disable 
BOOTP/DHCP. 

8.

Confirm that the Status panel message reads, ‘[Disable BOOTP] Command successful’. 

When the adapter power is recycled, it will use the assigned configuration and will not 
issue a BOOTP request. If you do not click Disable BOOTP/DHCP, the adapter clears 
the current IP configuration after a power cycle and will again begin sending BOOTP 
requests.

Summary of Contents for E3 Plus

Page 1: ...Solid State Overload or an 825 P Motor Protection System directly to an EtherNet IP network This document explains the basic steps needed to configure the E3 Plus EtherNet IP adapter Topic Page Intro...

Page 2: ...icularinstallation RockwellAutomation Inc cannotassumeresponsibilityorliabilityforactual use based on the examples and diagrams No patent liability is assumed by RockwellAutomation Inc with respect to...

Page 3: ...e autobaud enabled This is the default state of each of these devices Item Part Description 1 Status Indicators Four status indicators for the DeviceNet adapter and network connection 2 E3 Connector T...

Page 4: ...to configure a static IP address for each device To assign network parameters via the BOOTP DHCP utility perform this procedure 1 Start the BOOTP DHCP software Item Name Color State Description 1 POR...

Page 5: ...ry secondary server addresses and domain name 3 Click OK The Request History panel displays the hardware addresses of devices issuing BOOTP or DHCP requests 4 Double click the MAC address of the adapt...

Page 6: ...to the adapter this configuration can be permanently assigned to the adapter 7 To do so highlight the adapter in the Relation List panel and click Disable BOOTP DHCP 8 Confirm that the Status panel m...

Page 7: ...ellautomation com resources eds 1 When the web page for the link above comes up enter the following information 2 Select the file that relates to the E3 or 825 P module that is connected to the 2100 E...

Page 8: ...kwell Automation Publication 2100 IN090A EN P February 2012 3 Register a single file browse to the location of the EDS file and click Next 4 Click Next to accept the installation test results 5 Click...

Page 9: ...lus EtherNet IP adapter on an EtherNet IP network Follow these steps to configure a Logix controller for I O messaging 1 Right click on the EtherNet IP scanner in I O Configuration and select New Modu...

Page 10: ...using Input Instance 100 and Output Instance 103 for E3 standard or 105 for E3 Plus by default The size of the input connection and the output connection shall correspond to the size of the chosen ins...

Page 11: ...1 OutB 2 Fault Reset 3 Not Used 4 Not Used 5 Remote Reset 6 Not Used 7 Not Used Input Assembly Instance 100 Byte Size Contents 2 Bytes Header information Pad Word 2 Bytes Header information Pad Word 2...

Page 12: ...ation concerning related products from Rockwell Automation You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact...

Reviews: