Compact I/O Cable for DriveLogix5730 Controller
Publication 20D-IN008A-EN-P - April 2004
Step 1: Removing Power from Drive and Compact I/O
To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the +DC & –DC terminals of the
Power Terminal Block. The voltage must be zero.
Remove power before making or breaking cable connections. When
you remove or insert a cable connector with power applied, an
electrical arc may occur. An electrical arc can cause personal injury or
property damage by:
•
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
•
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.
L1
L2
L3
O
I
ATTENTION
!