ControlLogix ControlNet Interface Module
27
Publication
1756-IN607A-EN-P - February 2008
Any
Keeper:
Unconfigured
The network configuration
data maintained in flash
memory by the keeper object
has been erased or corrupted.
Perform any of these steps:
•
Use RSNetWorx software to
download or update the
keeper object in the module.
•
See Reset the Module to
the Original Factory Settings
on page 10.
Keeper:
Unconfigured
(data format
changed)
The network configuration
data maintained in flash
memory by the keeper object
is in a format incompatible
with the current revision of
firmware.
Perform any of these steps:
•
Use RSNetWorx software to
download or update the
keeper object in the module.
•
See Reset the Module to
the Original Factory Settings
on page 10.
Keeper:
Unconfigured
(slot
changed)
After the keeper object’s
network-configuration data
was downloaded, the module
was moved to a different spot
in the rack.
Perform any of these steps:
•
Return the module to the
proper slot.
•
Use RSNetWorx software to
download or update the
keeper object in the module.
•
See Reset the Module to
the Original Factory Settings
on page 10.
Keeper:
Unconfigured
(net address
changed)
The network address switches
on the module have been
changed since the keeper
object’s network-configuration
data was downloaded.
Perform any of these steps:
•
Return the network address
switches to their original
setting.
•
Use RSNetWorx software to
download or update the
keeper object in the module.
•
See Reset the Module to
the Original Factory Settings
on page 10.
Indicator
OK
Display
Cause
Recommended Action