24
ControlLogix ControlNet Interface Module
Publication
1756-IN607A-EN-P - February 2008
Red
(cont.)
Stop Service
Received
A non-redundant module is
placed into a redundant
secondary chassis. The
module was commanded to
stop functioning by the
redundancy module
(RM/SRM).
1. Remove the non-redundant
module from the redundant
secondary chassis
2. Replace the non-redundant
module with the redundant
module.
This could occur if a
1756-CN2/R module running
Boot code is inserted into a
chassis along with a
1756-SRM or 1756-RM
module.
For Redundant Control, the
1756-CN2 series B module is
designed to interoperate with a
1756-RM module. It should not be
used with a 1756-SRM module.
1. Insert the module into a
chassis that does not
contain a 1756-SRM or
1756-RM module.
2. Update the module’s
firmware using
ControlFLASH.
Flashing
red
Image
update
Needed
Boot image running.
Main firmware image needs
to be updated.
Update the module’s firmware
by using the ControlFLASH
utility.
DUPLICATE
NODE
DETECTED
The module’s network address
is the same as another
module’s on the link.
1. Remove power from the
chassis.
2. Remove the module from
the chassis.
3. Set the switches to their
final value. See page 10.
4. Replace the module in the
chassis.
5. Apply power to the chassis.
Flash in
progress
Flash update is in progress.
No action is required.
If communication to the
module is lost during a Flash
Update, this message will
continue to be displayed even
though the module will not be
able to finish the update.
You must remove power from
the module to recover, and
then flash again.
Indicator
OK
Display
Cause
Recommended Action