ControlLogix ControlNet Interface Module
25
Publication
1756-IN607A-EN-P - February 2008
Flashing
red (cont.)
TEST
Module is executing a
power-up test.
No action is required.
If the display persists for more
than 45 seconds, replace the
module because it has failed.
Green
OK
This is normal operation.
There is at least one
connection to or through the
module. No action is required.
INIT
Module is initializing.
No action is required.
PASS
This message is displayed
momentarily upon completion
of a successful power-up test.
No action is required.
CMPT
(1)
The secondary module is
compatible with its partner.
No action is required.
DSNP
(1)
The secondary module is
disqualified with no partner.
Check the corresponding slot
of the primary chassis for the
module type and revision.
PwDS
(1)
The module is primary with a
disqualified secondary
partner.
Check the type and revision of
the 1756-CN2 module.
PQgS
(1)
The module is primary with a
qualifying secondary partner.
Redundant system status. No
action is required.
PwQS
(1)
The module is primary with a
qualified secondary partner.
PwNS
(1)
The module is primary with no
secondary partner.
Check corresponding slot of
secondary chassis for correct
module.
QgS
(1)
The secondary module is
qualifying.
Redundant system status. No
action is required.
QS
(1)
The secondary module is
qualified.
A#xx
This message is the node
address where xx is an
address from 01...99.
No action is required.
Indicator
OK
Display
Cause
Recommended Action