Publication 1756-UM001G-EN-P - January 2007
Maintain the Battery
129
2.
Is the BAT LED off?
3.
Check that the battery module is correctly connected to the
controller.
4.
Check that the battery assembly is correctly connected to the
battery module.
5.
If the BAT LED remains on, install another battery assembly
(catalog number 1756-BATA).
6.
If the BAT LED remains on after you complete step 5, contact
your Rockwell Automation representative or local distributor.
Store Batteries
Additional Resources
For detailed guidelines on how to store batteries, see Guidelines for
Handling Lithium Batteries, publication AG 5-4, which comes with the
battery.
If
Then
Yes
The battery module is correctly installed.
No
ATTENTION
Follow these general rules to store your batteries:
•
Store batteries in a cool, dry environment. We recommend
25 °C (77 °F) with 40…60% relative humidity.
•
You may store batteries for up to 30 days in temperatures from
-45...85 °C (-49...185 °F), such as during transportation.
•
To avoid leakage or other hazards, do not store batteries above
60 °C (140 °F) for more than 30 days.
Summary of Contents for controllogix 1756-L55M12
Page 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Page 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Page 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Page 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Page 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Page 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...