98
Rockwell Automation Publication 1769-UM022C-EN-P - June 2018
Chapter 6
Add and Configure Standard I/O Modules
Configure Standard
Distributed I/O Modules on
an EtherNet/IP Network
Your Compact GuardLogix 5370 controller system can use distributed I/O
modules on an EtherNet/IP network.
Complete these steps to configure distributed I/O modules on an EtherNet/IP
network.
1. In the Controller Organizer, select and right-click the 1734-AENT
under Ethernet, and choose New Module.
2. Select the desired Ethernet adapter and click Create.
IMPORTANT
When you add distributed I/O modules, remember to count the remote
Ethernet adapter to remain within the maximum number of EtherNet/IP
network nodes limitation for your controller.
The remote I/O modules that are connected to the controller via the
Ethernet adapter are not counted toward the maximum Ethernet node limit
for the controller.
For more information on node limitations, see
.