Rockwell Automation Publication 857-UM002C-EN-P - February 2018
37
Configure the 857-RAD Analog Outputs
Appendix A
Example #3 – mA Output Scaling for Bidirectional Power
• Minimum Analog Output value = 4 mA
• Maximum Analog Output value = 20 mA
• Linked minimum value = -2000 kVAR
• Linked maximum value = 6000 kVAR
• Modbus minimum value = 4000
(Minimum Analog Output value x 1000)
• Modbus maximum value= 20,000
(Maximum Analog Output value x 1000)
Figure 15 - mA Output Scaling for Bidirectional Power
Analog
Output
Summary of Contents for 857-RAA
Page 1: ...857 RAA 857 RAD RTD Scanner Catalog Numbers 857 RAA 857 RAD User Manual OriginalInstructions...
Page 6: ...6 Rockwell Automation Publication 857 UM002C EN P February 2018 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 1 Layout Notes...
Page 14: ...14 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 2 Application Notes...
Page 41: ......