Chapter 4
Configure the Base 857 Relay
External Analog Outputs for
857-RAD Scanner
The 857-RAD scanner is equipped with four individual isolated analog
outputs. If used, these outputs must be configured within the base relay for
proper operations. Each analog output has a fully configurable output current
range. Typical range configurations would be 0…20 mA or 4…20 mA. More
dynamic ranges like 0…1 mA, 0…5 mA, or 10…20 mA can be configured freely
as long as the boundary values are within the 0…20 mA range.
Table 9 - 857-RAA/RAD External I/O Registers
Modbus Register
Properties
RTD Channel 1 resistance
301
Read
RTD Channel 2 resistance
302
Read
RTD Channel 3 resistance
303
Read
RTD Channel 4 resistance
304
Read
RTD Channel 5 resistance
305
Read
RTD Channel 6 resistance
306
Read
RTD Channel 7 resistance
307
Read
RTD Channel 8 resistance
308
Read
RTD Channel 9 resistance
309
Read
RTD Channel 10 resistance
310
Read
RTD Channel 11 resistance
311
Read
RTD Channel 12 resistance
312
Read
mA-input 1
(1)
(1) 857-RAD only.
313
Read
mA-input 2
(1)
314
Read
mA-input 3
(1)
315
Read
mA-input 4
(1)
316
Read
PTC-resistance
(1)
317
Read
mA-output 1
(1)
318
Read / Write
mA-output 2
(1)
319
Read / Write
mA-output 3
(1)
320
Read / Write
mA-output 4
(1)
321
Read / Write
Summary of Contents for 857-RAA
Page 1: ...857 RAA 857 RAD RTD Scanner Catalog Numbers 857 RAA 857 RAD User Manual OriginalInstructions...
Page 6: ...6 Rockwell Automation Publication 857 UM002C EN P February 2018 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 1 Layout Notes...
Page 14: ...14 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 2 Application Notes...
Page 41: ......