28
Rockwell Automation Publication 857-UM002C-EN-P - February 2018
Chapter 4
Configure the Base 857 Relay
Linked Val. Min
See
Configure the 857-RAD Analog Outputs
on page 35
AO Link’s user defined Minimum
Value
Allows scaling of the mA Output parameter
Linked Val. Max
See
Configure the 857-RAD Analog Outputs
on page 35
AO Link’s user defined maximum
value
Allows scaling of the mA Output parameter.
Ao Slave address
1…247
RTD Modbus slave address
Value must match the hardware Address ss defined by the
switches on the 857-RAD
Ao Modbus address
See
Configure the 857-RAD Analog Outputs
on page 35
1
318
2
319
3
320
4
321
Although there are 16 locations available, only 4 can be assigned
(857-RAD). Addresses are by default numbered from 1 to 16.
However the address value must be set according to the Modbus
registers values, meaning that:
Analog Output 1 — Modbus 318
Ao Register type
HoldingR
Holding register
According to the Modbus Protocol a Holding Register is a 16-bit
word register which can be read or written.
Modbus Min
See
Configure the 857-RAD Analog Outputs
on page 35
This is the minimum value which is
sent to the 857-RAD via Modbus
protocol in order to set the minimum
value for the mA Min parameter.
Typical values;
mA Min = 0 is equal to a Modbus Min = 0
The relationship between these two parameters is 1:1000.
See
Configure the 857-RAD Analog Outputs on page 35
.
Modbus Max
See
Configure the 857-RAD Analog Outputs
on page 35
This is the maximum value which is
sent to the 857-RAD via Modbus
protocol in order to set the maximum
value for the mA Max parameter.
Typical values;
mA Max = 20 is equal to a Modbus Max = 20000
The relationship between these two parameters is 1:1000.
See
Configure the 857-RAD Analog Outputs on page 35
AO Counter
0 …
Error counter for AO
It increments itself if either AO Slave Address or Ao Register
Address are not set correctly
Table 10 - 857-RAD External Analog Outputs Parameter Setup (Continued)
Parameter
Value
Explanation
Notes
Table 11 - Measurands that can be Assigned to Analog Outputs
Measurement Value
Description
Extended Description
Measurand
P
Active power
Real power
[kW]
Q
Reactive power
Reactive power flow
[kvar]
S
Apparent power
Root-mean-square (rms) current by the root-mean-square voltage
[kVA]
P.F.
Power factor
Measured power factor
-1 to 1
f
Frequency
Measured frequency
[Hz]
cosphi
Cosine phi
(kW/kVA)
- 1 to 1
IL1
Phase current IL1
Phase A current
[A]
IL2
Phase current IL2
Phase B current
[A]
IL3
Phase current IL3
Phase C current
[A]
IL
Average current (IL1+IL2+IL3)/3
Motor or feeder average current
[A]
U12
Phase-to-phase voltage U12
Line-to-line voltage
[V]
U23
Phase-to-phase voltage U23
Line-to-line voltage
[V]
31
Phase-to-phase voltage U31
Line-to-line voltage
[V]
UL
Average for the three phase voltages
Line to Line Average Voltage (LL)
[V]
UL1
Phase-to-earth voltage UL1
Phase-to-ground voltage
[V]
UL2
Phase-to-earth voltage UL2
Phase-to-ground voltage
[V]
UL3
Phase-to-earth voltage UL3
Phase-to-ground voltage
[V]
UPhase
Average Voltage (UL1+UL2+UL3)
Line to Neutral Average Voltage (LN)
[V]
IFault
Latest overcurrent fault level
Pu value of current
[pu]
Summary of Contents for 857-RAA
Page 1: ...857 RAA 857 RAD RTD Scanner Catalog Numbers 857 RAA 857 RAD User Manual OriginalInstructions...
Page 6: ...6 Rockwell Automation Publication 857 UM002C EN P February 2018 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 1 Layout Notes...
Page 14: ...14 Rockwell Automation Publication 857 UM002C EN P February 2018 Chapter 2 Application Notes...
Page 41: ......