22
Rockwell Automation Publication 6181X-UM001C-EN-P - July 2015
Chapter 2
Installation
Mounting Clearance
Requirements
Figure 2 - Minimum Clearances
IMPORTANT
Because of self-heating, do not operate the computer in an enclosure by using
the minimum clearances unless adequate ventilation or other methods are
used to lower the temperature within the enclosure.
Allow enough clearance to install or remove peripheral components, such as
internal drives.
The minimum required enclosure size (HxWxD) is 403 x 497 x 154 mm
(15.87 x 19.57 x 6.06 in.).
Right and left are based on facing the front of the computer.
Item
Description
Value
1
Top
50 mm (2 in.)
2
Left (for airflow)
50 mm (2 in.)
3
Rear
50 mm (2 in.)
4
Right (for airflow and drive access)
127 mm (5 in.)
5
Bottom (for I/O port access and ventilation)
102 mm (4 in.)
4
5
3
1
2