264
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix B
Module Tag Definitions
Ptxx.NoLoad
BOOL
Indicates that the signal wire has been disconnected from
one of its terminals or the RTB has been removed. Used
with Output channels.
• 0 = No fault
• 1 = Fault
Ptxx.ShortCircuit
BOOL
Indicates an output short circuit or overcurrent.
• 0 = No short circuit
• 1 = Short circuit or overcurrent
Schedulex
SINT
Indicates which schedule to load from 32 available
schedules.
• 1…32 = Valid schedule
• 0, 129…255 = No schedule
Schedulex.State
SINT
Current state of the Tagschedule at index x.
• 0 = Inactive
• 1 = Active – schedule is next to be applied to
any of the outputs.
• 2 = Current – schedule is not the next to be
applied one of the outputs.
• 3 = Expired – schedule has been applied.
• 4 = Discarded – scheduled but mask was off,
or the requested schedule was late (received
after its scheduled application time) and a
more recent schedule has already been applied
to that output point.
• 5 = Late – received schedule after the time it
is to be applied.
Schedulex.ScheduleNumber
SINT
Echo of ScheduleNumber from the output image.
• 0…3
LateScheduleCount
INT
Count of schedules that arrive late. That is, the arrival time
is after scheduled time. Counter rolls over every 65535 late
updates. The output is still be driven to new state if this is
the most recent schedule for that point. Useful in
indicating that network delays/losses are causing
scheduling issues.
All values.
LostScheduleCount
INT
Increments whenever the schedule sequence number in
the output tag skips a value, which can indicate a lost
schedule. Counter rolls over every 65535 lost updates.
All values.
Table 84 - 5069-OB16F Module Input Tags
Name
Size
Definition
Valid Values