18
Rockwell Automation Publication 2711PC-UM002F-EN-P - February 2020
Chapter 2
Install the Terminal
Mounting Clearances
Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cabling. Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminal must be 0…55 °C (32…131 °F).
Panel Guidelines
The terminals are panel-mounted devices intended to mount in the door or wall
of a NEMA rated, UL Type rated, or IP rated enclosure:
•
Supporting panels must have a mounting thickness of 1.5…4.8 mm
(0.060…0.188 in.).
•
The material strength and stiffness of the panel must be sufficient to hold
the terminal and maintain an appropriate seal against water and dust.
•
The panel surface must be flat and free of imperfections to maintain an
adequate seal and NEMA and UL Type ratings.
Panel Cutout Dimensions
Use the full-size template shipped with your product to mark the cutout
dimensions.
Table 12 - Minimum Required Clearances
Product Area
Minimum Clearance
Top
51 mm (2 in.)
Bottom
102 mm (4 in.)
(1)
(1) A clearance of 102 mm (4 in.) is sufficient on the side of the terminal to insert and remove an SD card, and on the bottom of
the terminal for connections.
Side
25 mm (1 in.)
(1)
Back
0 mm (0 in.)
Table 13 - Panel Cutout Dimensions
Terminal Type
Input Type
Height, mm (in.)
Width, mm (in.)
400
Keypad or keypad/touch
123 (4.86)
156 (6.15)
600
Touch
123 (4.86)
156 (6.15)
1000
Touch
224 (8.8)
305 (12.00)